General Site Preparation Guidelines
Electrical Factors
Chapter 2
12
•
Smoke detectors
•
Fire and temperature alarms
•
Fire extinguishing system
Additional safety devices are:
•
Circuit breakers
•
An emergency power cutoff switch
•
Devices specific to the geographic location i.e., earthquake protection
Lighting Requirements for Equipment Servicing
Adequate lighting and utility outlets in a computer room reduce the possibility of accidents during equipment
servicing. Safer servicing is also more efficient and, therefore, less costly.
For example, adequate lighting reduces the chances of connector damage when cables are installed or
removed.
The minimum recommended illumination level is 70 foot-candles (756 lumens per square meter) when the
light level is measured at 30 inches (76.2 cm) above the floor.
Working Space for Server Access
The recommended working space for performing maintenance on the server is three feet. The work space
shall permit at least a 90 degree opening of equipment doors or hinged panels. When planning for the working
space area, consider whether access to the server will be at the front, the side, or the rear of the server.
Power Consumption
When determining power requirements, you must consider any peripheral equipment that will be installed
during initial installation or as a later update. Refer to the applicable documentation for such devices to
determine the power required to support these devices.
Electrical Load Requirements (Circuit Breaker Sizing)
NOTE
Local Authority Has Jurisdiction [LAHJ] and should make the final decision regarding
adherence to country-specific electrical codes and guidelines.
It is good practice to derate power distribution systems for one or more of the following reasons:
•
To avoid nuisance tripping from load shifts or power transients, circuit protection devices should never be
run above 80% of their root-mean-square (RMS) current ratings.
•
Safety agencies derate most power connectors to 80% of their RMS current ratings.
Power Quality
The hp Integrity rx5670 is designed to operate over a wide range of voltages and frequencies. The server is
tested and shown to comply with EMC Specification EN50082. However, damage can occur if these ranges are
exceeded. Severe electrical disturbances can exceed the design specifications of the equipment.
Summary of Contents for Integrity rx5670
Page 4: ...Contents 4 Power Cable 43 Glossary 45 ...
Page 10: ...System Specifications Environmental Specifications Chapter 1 10 ...
Page 30: ...General Site Preparation Guidelines Space Requirements Chapter 2 30 Equipment cable routing ...
Page 42: ...Power Plug Configuration Male End of Power Cable Chapter 3 42 Figure 3 10 GB 1002 Plug ...
Page 44: ...Power Plug Configuration Power Cable Chapter 3 44 ...