General Site Preparation Guidelines
Facility Characteristics
Chapter 2
28
Windows
Avoid housing computers in a room with windows. Sunlight entering a computer room may cause problems.
Magnetic tape storage media is damaged if exposed to direct sunlight. Also, the heat generated by sunlight
places an additional load on the cooling system.
Concentrated load
b
1250 lb (567 kg)
Ultimate load
4,000 lb (1814 kg) per panel
Rolling load
400 lb (181 kg)
Average floor load
500 lb (227 kg)
a. From Table 2-2 on page 27
b. With 0.08 in (0.2 cm) of span maximum deflection
Table 2-3
Typical Raised Floor Specifications (Continued)
Item
a
Rating