HSG80 Array Controller V8.7 Maintenance and Service Guide
4–11
Replacement Procedures for Model 2200 Enclosure Elements
12. If using a Windows NT or Windows 2000 platform, restart the server.
13. Disconnect the PC or terminal from the controller maintenance port.
Replacement Procedures for Controller and Cache
Modules in a Dual-Redundant Controller Configuration
Follow the instructions in this section to replace modules in a dual-redundant
controller configuration (see Figure 4–6).
Figure 4–6: Dual-redundant controller configuration in a Model 2200 enclosure
The following sections provide procedures for:
•
Replacing both the controller and cache module
•
Replacing only a controller
•
Replacing only a cache module
1
Controller A
2
Controller B
3
Cache A
4
Cache B
5
Fiber optic cables with extender clips
4
1
2
3
5
CXO7179A