Planning the installation 8
Grounding requirements
This equipment must be grounded properly for proper operation and safety. In the United States, you
must install the equipment in accordance with NFPA 70, 1999 Edition (National Electric Code), Article
250, as well as any local and regional building codes.
In Canada, you must install the equipment in accordance with Canadian Standards Association, CSA
C22.1, Canadian Electrical Code.
In all other countries, you must install the equipment in accordance with any regional or national electrical
wiring codes, such as the International Electrotechnical Commission (IEC) Code 364, parts 1 through 7.
Furthermore, you must be sure that all power distribution devices used in the installation, such as branch
wiring and receptacles, are listed or certified grounding-type devices.
Because of the high ground-leakage currents associated with this equipment, Hewlett Packard Enterprise
recommends the use of a PDU that is either permanently wired to the building’s branch circuit or includes
a nondetachable cord that is wired to an industrial-style plug. NEMA locking-style plugs or those
complying with IEC 60309 are considered suitable for this purpose. Using common power outlet strips to
supply power to this equipment is not recommended.
Summary of Contents for apollo 4510 gen9
Page 20: ...Identifying components and LEDs 20 Optional 8 LFF drive cage bay numbering ...
Page 32: ...Installing the chassis 32 Installing a management module Install the component as indicated ...
Page 60: ...Support and other resources 60 ...
Page 61: ...Support and other resources 61 ...
Page 64: ...Acronyms and abbreviations 64 UPS uninterruptible power system USB universal serial bus ...
Page 68: ...Index 68 W warranty 46 warranty information 46 website Hewlett Packard Enterprise 54 ...