Periodic maintenance 69
Component to be inspected
Task
Frequency
Capable Party
—
Exterior water proofing check for
ingress using water hose
Annually
Certified facilities
personnel
Switchgear
Component to be inspected
Task
Frequency
Capable Party
Switchgear
Infrared inspection of all electrical
power connections while under
normal load
Annually
HP and certified
facilities personnel
—
Grounding and electrical systems Annually
HP and certified
facilities personnel
—
Panel operational testing
Annually
HP and certified
facilities personnel
—
Breakers/disconnects
Annually
HP and certified
facilities personnel
Third-party components
See the
Operations and Maintenance Manual for the HP Performance Optimized Datacenter 40c
for other
required maintenance items.
UPS
Component to be inspected
Task
Frequency
Capable Party
UPS
Vacuum Pump oil change
Annually
HP
—
Log file review
Annually
HP
—
Calibration verification
Annually
HP
—
Telemetry review
Annually
HP
—
Replace bearings
Every 2.5 to 3
years
HP