Illustrated parts catalog 10
Electrical panels
WARNING:
To avoid the risk of personal injury or loss of life, all personnel must comply with PPE
requirements when opening or working inside areas of the HP POD 40c G2 that are marked as
hazardous voltage, per NFPA 70E in accordance with NEC (NA) and IEC (EMEA and APJ).
WARNING:
To avoid the risk of personal injury or loss of life, all personnel must comply with
electrical warning labels when operating and maintaining the electrical panels and systems of the
HP POD 40c G2.
End view shown
Item
Component
Description
1
Fire box*
Connection location for fire emergency and VESDAnet signals
2
Demarcation box*
Customer communication connection point for the following
components:
•
ECS
•
Security
•
Phone
3
415 Y/240 V 3-phase,
4-wire, 800 A electrical
panel
Feed A power for critical IT loads (electrical busways) and house power
4
415 Y/240 V 3-phase,
4-wire, 800 A electrical
panel
Feed B power for critical IT loads (electrical busways) and house power
*The demarcation box and the fire box are communication data points that are provided on the POD by HP. Connecting
these data points is the responsibility of the customer, unless an approved Statement of Work is initiated.
Main breaker locations