Illustrated parts catalog 11
End view shown
Cooling system component identification
The heat exchanger access hatches are located on top of the POD. The hatches are coated with a durable
finish to prevent corrosion.
Side view shown
Item
Component
Description
1
Heat exchangers
Use facility chilled water to cool the air in the HP POD 40c G2
2
Heat exchanger fan
banks
Operate at variable speeds to maintain the preprogrammed differential
pressure setpoint and the hot aisle temperature setpoint
3
Chilled water supply Supplies facility chilled water to cool the HP POD 40c G2
4
Chilled water return
Returns heated chilled water to the facility
HP POD 40c G2 racks
The HP POD 40c G2 contains a total of 20 IT racks.