P/N 480-0005-00-15
5-7
Chapter 5: Working with SNMP
2. Type
telnet
in the Open box and click on
Ok
.
3. Click
Connect> Remote System.
4. In the
Host Name
window, enter the IP address of the unit from which you would like to view alarms.
5. In the port window, choose telnet (port 23 is the default port for a telnet session).
6. From the
TermType
drop down list, select
vt100
.
7. Click
Connect.
A telnet session will be displayed. (To exit a telnet session at any time, type
exit
at the
prompt.)
8. Enter the same password you set via CLI.
9. At the c
onfig - MasterChassis prompt
, type
set snmptrapip1 <ip>.
For example, type
set snmptrapip1
208.226.140.12.
This will assign index of 1 to indicate the first network manager being assigned to that
Tenor CMS unit and assign the IP address 208.226.140.12 as the network manager. To assign the second
snmptrap ip, type
set snmptrapip2 <ip>
and the third type set
snmptrapip3 <ip>
.
10. Repeat step 9 for each network manager (up to 3).
11. Type submit. The new IP address(es) will be submitted to the applicable Tenor CMS unit.