Display

Possible Cause

Handling Suggestions

Over Temperature

The temperature inside the inverter 

is higher than the permissible 

range.

1. Make sure that the installation complies with the 

instructions from User Manual.

2. Check whether the alarm “Fan Fault” occurs. If so, 

replace the faulty fan.

3. If the alarm persists, contact Hoymiles technical 

support team.

Isolation Fault

The ground insulation impedance 

of the PV string is too low.

1. Use a multimeter to determine if the resistance 

between the earth and the inverter frame is close to zero. 

If not, please ensure that the connection is good.

2. If the humidity is too high, an isolation fault may occur. 

Attempt to restart the inverter. If the fault persists, check 

it again when the weather turns fine.

3. Check the resistance to ground from the PV module/

cable. Take corrective measures in case leading to a short 

circuit or damaged insulation layer.

4. If the alarm persists, contact Hoymiles technical 

support team.

Arc Fault

The inverter detects that there is 

an arc fault.

1. Disconnect the DC switch and check whether DC cables 

are damaged and whether the wiring terminals are loose 

or in poor contact. If so, take corresponding corrective 

measures.

2. After taking corresponding measures, reconnect the 

DC switch. 

3. If the alarm persists, contact Hoymiles technical 

support team.

EPS Load 

Overpower

The EPS load power is higher than 

the permissible range.

1. Reduce the power of EPS loads, or remove some EPS 

loads. The inverter will restart automatically.

2. If the alarm persists, contact Hoymiles technical 

support team.

Meter Reverse 

Connection

The inverter detects that the Meter 

or CT is reverse connected.

1. Make sure that the installation complies with the 

instructions from User Manual.

2. If the alarm persists, please contact Hoymiles technical 

support team.

Meter 
Communication 
Fault

The inverter detects that there 
is a meter communication fault.

1. Check whether the Meter communication cable and 

terminal are abnormal.

2. Reconnect the Meter communication cable.

3. If the alarm persists, please contact Hoymiles technical 

support team.

Battery Reverse 

Connection

The inverter detects that the 

battery wirings are reversely 

connected.

1. Check the battery for polarity correctness, and correct 

it if necessary.

2. If the alarm persists, please contact Hoymiles technical 

support team.

Battery Voltage 

Fault

The battery voltage is higher than 

the permissible range.

1. Check if the battery input voltage is within the normal 

range.

2. If the alarm persists, please contact Hoymiles technical 

support team.

BMS 

Communication 

Fault

The inverter detects that there is a 

BMS communication fault.

1. Check whether the BMS communication cable and 

terminal are abnormal.

2. Reconnect the BMS communication cable.

3. If the alarm persists, please contact Hoymiles technical 

support team.

Summary of Contents for HYT-10.0HV-EUG1

Page 1: ...Open Energy for All USER MANUAL HYT 5 0HV EUG1 HYT 6 0HV EUG1 HYT 8 0HV EUG1 HYT 10 0HV EUG1 HYT 12 0HV EUG1 Region Global REV1 0 hoymiles com...

Page 2: ...ng Inverter 15 3 3 Electrical Wiring Connection 15 3 3 1 Grounding Connection 15 3 3 2 PV Wiring Connection 16 3 3 3 Battery Wiring Connection 17 3 3 4 AC Wiring Connection 18 3 3 4 1 Grid Connection...

Page 3: ...n death or serious injury Indicates a hazard with a low level of risk that if not avoided can result in minor or moderate injury Indicates a situation that if not avoided can result in property damage...

Page 4: ...ould be taken Please consider the actual conditions on site when performing operations Any damage caused by a violation of the safety instructions in this manual shall not be the responsibility of Hoy...

Page 5: ...s should be grounded for safety reasons Ensure that existing wiring is in good condition and no wire is undersized Do not disassemble any parts of inverter which are not mentioned in installation Auth...

Page 6: ...ystem s performance over time offering superior energy production H I J K A B C D E F G The image shown here is for reference only The actual product received may differ Object Description A DC Switch...

Page 7: ...circle LEDs off No BMS communication RUN Off Inverter is not operating Blink 1 Inverter is booting Blink 2 Inverter is in bypass mode On Inverter is operating PV Off PV voltage is low Blink 1 PV powe...

Page 8: ...m charge power the excess solar energy is fed back into the grid or limited if necessary At night the battery discharge for the loads first and once the battery power is insufficient the grid supplies...

Page 9: ...y can be forced to charge from the grid during the preset charge time For instance the battery could be charged or discharged according to valley or peak electricity price Power flow of back up mode B...

Page 10: ...ell as for self consumption of solar energy It can either form a DC coupled system for a new installation or an AC coupled system to retrofit existing installations This diagram is a simplified system...

Page 11: ...ds on Loads Main Breaker 30 mA RCD HYT 6 0HV EUG1 25A 600V DC Breaker 16A 230V AC Breaker 25A 230V AC Breaker HYT 8 0HV EUG1 40A 600V DC Breaker 20A 230V AC Breaker 32A 230V AC Breaker HYT 10 0HV EUG1...

Page 12: ...25A 600V DC Breaker 16A 230V AC Breaker 25A 230V AC Breaker HYT 8 0HV EUG1 25A 600V DC Breaker 20A 230V AC Breaker 32A 230V AC Breaker HYT 10 0HV EUG1 40A 600V DC Breaker 25A 230V AC Breaker 32A 230V...

Page 13: ...With the addition of the hybrid inverter existing PV system can be retrofitted to be a PV ESS allowing more self consumption energy and more backup energy The detailed wiring of your system depends on...

Page 14: ...anual 2022 Hoymiles Power Electronics Inc All rights reserved 13 3 Installation Instruction 3 1 Packing List Please ensure that none of the components listed below are missing or damaged upon receipt...

Page 15: ...shelter from direct sunlight or bad weather such as snow rain or lightning 2 The inverter should be installed on a solid surface which is suitable for the inverter s dimensions and weight 3 The invert...

Page 16: ...holes and tighten them Then install the wall bracket with the expansion screws Please confirm that the bracket is firmly attached to the mounting surface 3 4 Step 5 Mount the inverter on the bracket...

Page 17: ...of an incompatible terminal shall not be covered by the warranty Please make sure the connectors are correct not the battery connectors as they look similar NOTICE Procedure Step 1 Unscrew the PV con...

Page 18: ...ick if it is plugged in correctly 3 2 1 3 BAT BAT 4 Click 4 3 3 3 Battery Wiring Connection This section mainly describes the cable connections on the inverter side Refer to the instructions supplied...

Page 19: ...r electrical connections are completed Procedure Step 1 Thread the AC cable of appropriate length through the waterproof terminal Remove the cable jacket by 20 25 mm and strip the wire insulation by 7...

Page 20: ...sure all requirements listed below are followed Use the Grid Connector from the accessory box Damage to the device due to the use of an incompatible connector shall not be covered by the warranty An i...

Page 21: ...port on the communication interfaces are as follows Label Description Meter 485A 485B For the Smart Meter BMS CANH CANL 485A 485B For Li ion battery communication via CAN or RS485 DRM D1 5 D2 6 D3 7...

Page 22: ...the parts in sequence 1 2 3 2 Step 3 Strip the insulation layer of the communication cable with an ethernet wire stripper and lead the corresponding signal cables out Insert the stripped communicatio...

Page 23: ...he inverter via RS485 communications One smart meter can be used with only one HYT HV inverter Three CTs must be used for one smart meter and must be connected on the same phase with the smart meter p...

Page 24: ...Step 1 Peel the stickers off from the communication port 1 Step 2 Unscrew the communication box counterclockwise Disassemble the parts in sequence 1 2 3 2 Step 3 Strip the insulation layer of the com...

Page 25: ...Connection There is an integrated DI IN IN as the dry contact input to the bypass contactor of the inverter The connection method is the same as that described in Chapter 3 3 5 3 Wiring the No 1 and N...

Page 26: ...parallel function is in developing and could be realized through OTA For more information please contact Hoymiles technical support team 3 3 6 DTS Connection DTS WIFI G1 and DTS 4G G1 Procedure Steps...

Page 27: ...for details Indicator Status Description RUN ON DTS is powered on OFF DTS is not powered on COM ON Proper communication with the inverter OFF Improper communication with the inverter NET ON Proper com...

Page 28: ...een the mobile phone and DTS Configure the parameters in Storage Toolkit and Network Config referring to 3 4 2 S Miles Cloud APP Then use the System Self test function to detect if there is a problem...

Page 29: ...ange 3 If the alarm persists please contact Hoymiles technical support team Grid Underfrequency The grid frequency is lower than the permissible range No Grid The inverter detects that there is no gri...

Page 30: ...If the alarm persists contact Hoymiles technical support team EPS Load Overpower The EPS load power is higher than the permissible range 1 Reduce the power of EPS loads or remove some EPS loads The in...

Page 31: ...MS Try to restart the battery If the fault persists contact the battery manufacturer BMS Battery Fault The inverter detects that there is a battery fault from BMS Try to restart the battery If the fau...

Page 32: ...1 2 Max PV Input Current A 14 14 14 14 14 14 14 28 14 28 Short circuit Current of PV Input A 17 17 17 17 17 17 17 34 17 34 AC Input and Output On grid Nominal Output Apparent Power VA 5000 6000 8000 1...

Page 33: ...Integrated AC Short Current Protection Integrated AC Overvoltage and Undervoltage Protection Integrated Surge Protection DC Type II AC Type III General Dimension W H D mm 502 486 202 Weight kg 26 Moun...

Page 34: ...c All rights reserved 33 6 Contact Information S Miles Installer S Miles Enduser China No 18 Kangjing Road Hangzhou China 86 571 2805 6101 General inquiry info hoymiles com Technical support service h...

Reviews: