MAINTENANCE
Parameters
Description
Unit
Level
System setting values
45-UG (1550)
33 2FL 32801 Fan ramp-up during operation
rpm/s
OEM
100
34
2FM
32802 Fan ramp-down during operation
rpm/s
OEM
100
35 2FN 32803 Fan follow-on time after a lock-out
sec
OEM
180
36 2FO 32804 Fan speed after shut-down
in normal operation or when locked
rpm
OEM
1600
37 2FR 32805 Fan follow-on time after operation
or blocking
min
OEM
3
38 2FU 32806 Fan speed for boiler operation in frost protection mode
rpm
OEM
1600
39
2GA 32807 Waiting period after opening of main gas valve or
activation of boiler room fan
min
OEM
0
40 2GB 32808 External main gas valve / boiler room fan available
OEM
1
41 2HA
32809
Heating pump follow-on time
or shut-off device after heat demand
min
HF
5
42 2HD 32810 Summer operation (“summer kick”)
sec
OEM
10
43 2IA 32811 Ignition (0-> internal, 1-> in external, 2-> external)
OEM
2
44
2KM
32812 Stepped modulation
(0-> off, 1-> rising, 2-> rising and falling)
HF
1
45 2LA 32813 Action mode fault relays
HF
2
46 2NA 32814 ADC/4 value at 0 bar
OEM
25
47 2NB 32815
ADC/4 value at 10 bar and BIC 960 V.3
OEM
225
48 2IB 32816 Extended external ignition time
sec
OEM
8
49
2CB 32817 Vacuum and overpressure switch (fan)
activation / deactivation
(0 -> deactivated, 1 -> activated)
OEM
1
50 2CC 32818 Reserve
OEM
0
Adjustments for liquid gas
27 2FF
32795 Fan speed first phase pre-vent
rpm
OEM
-
28 2FG
32796
Start rpm
rpm
OEM
-
29
2FH
32797 Maximum fan speed
rpm
OEM
-
30 2FI
32798 Minimum fan speed
rpm
OEM
-
36 2FO 32804 Fan speed after shut-down during normal operation or
lock-out
rpm
OEM
-
* for fan type: G3G250 MW50-11
Parameter 26: 4
for fan type: G3G250 MW00-XB
Parameter 26: 5