INSTAllATION
4.
Installation
4.1
Safety instructions
CAUTION
Cutting injuries as a result of sharp edges.
Handle parts of the casing carefully and avo-
id contact with sharp edges.
4.2
Requirements on the boiler room
§
Regarding the building specifications for boi
-
ler rooms, regulations specific to the state or
country are to be observed.
Regarding the ventilation of boiler rooms, re-
gulations specific to the state or country are to
be observed.
!
CAUTION
Gas boilers must not be installed in rooms
in which halogen compounds occur and can
get into the combustion air (e.g. washrooms,
drying rooms, hobby rooms, hairdressers).
!
CAUTION
Halogen compounds can be created, for ex-
ample, by cleansing and degreasing agents,
solvents, glue and bleaches
Always make sure there is an adequate supply of com-
bustion air to the boiler room.
This contributes to correct function of all the firing devices
that are operated there, and provides oxygen for the ope-
rating personnel to breathe.
Make sure there is an adequate supply of fresh air to the
boiler room, according to local regulations.
4.2.1 Room air dependent installation
Binding values for the size of supply air openings are not
generally specified in the relevant regulations. It is merely
required that no partial vacuum in excess of 3 N/m
2
oc-
curs. The locally applicable regulations must be complied
with: