25
4 217 901 / 02
TECHNICAl INFORMATION
4.6.2 Hydraulic integration
A mixer must be installed when combining a calorifier with underfloor heating. A minimum circulation water quantity is
not required.
4.6.2.1 Example application
Gas boiler with
-
calorifier
- 1 direct circuit and 1- mixer circuit(s) (HT/LT separation)
Hydraulic schematic BDEE050
1
A
B
D
E
C
F
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
A
B
D
E
C
F
BDEE050.dwg
Achtung !
Für die Installation muss das anlagenbezogene Schema verwendet werden!
Attention!
This is just a schematic. For installation please use the detail-plan!
Attenzione!
Per la messa in opera, utilizzare le schema dettagliato!
Attention!
Pour la réalisation pratique de l'installation, il faut utiliser le schéma détaillé!
Datum:
Datei:
Version:
Blatt:
Hydr.
Verbindungshinweise /
Notice / Nota / Remarque:
1
BDEE050
Name:
00
HATI
05.03.2018
SLP
T
T
AF
RBM
TTE-GW
TTE-WEZ
MK1
T
T
VF1
YK1
DKP
T
T
TTE-FE
HK
SF
T
HT
NT
UltraGas
P
T
P
P
max
STB
MK2
T
T
B1.2
VF2
YK2
Fig. 18
TTE-H-Gen TopTronic
®
E basic module heat generator (installed)
VF1
Flow temperature sensor 1
MK1
Pump, mixer circuit 1
YK1
Actuator, mixer 1
AF
Outdoor sensor
SF
Calorifier sensor
HCP
Pump for heating circuit without mixer
SLP
Calorifier charging pump
Optional
RBM
TopTronic
®
E room control module
TTE-GW
TopTronic
®
E Gateway
TTE-FE HK TopTronic
®
E module expansion heating circuit
VF2
Flow temperature sensor 2
B1.2
Flow temperature monitor (if required)
MC2
Pump, mixer circuit 2
YK2
Actuator, mixer 2
NOTICE
Please close unused connections tightly.
Important information:
• The example schematics merely show the
basic principle and do not contain all infor-
mation required for installation. Installation
must be carried out according to the condi-
tions on site, dimensioning and local regu-
lations.
•
With underfloor heating, a flow temperature
monitor must be installed.
•
Shut-off devices to the safety equipment
(pressure expansion tank, safety valve,
etc.) must be secured against unintentional
closing!
• Install sacks to prevent single-pipe gravity
circulation!
• An automatic air vent (AAV) must be ins-
talled before the shut-off valve. This is not
supplied by Hoval.
Summary of Contents for UltraGas 1550