7
4 213 894 / 01
TECHNICAL INFORMATION
3.
Technical information
3.1
Technical Data
Type
(80)
•
Nominal heat output 80/60°C with natural gas
1
kW
15,8-72,4
•
Nominal heat output 40/30 °C with natural gas
1
kW
17,3-80,0
•
Nominal heat output 80/60 °C propane gas
3
kW
19,5-72,4
•
Nominal heat output 40/30 °C propane gas
3
kW
21,6-80,0
• Nominal load with natural gas
1
kW
16,5-75,0
• Nominal load with propane gas
3
kW
20,0-75,0
•
Working pressure heating maximum/minimum.
bar
4,0/1,5
• Working temperature maximum
°C
85
•
Boiler water content
l
10
•
Minimum water flow
l/h
800
•
Boiler weight (without water content)
kg
107
•
Boiler efficiency at 30% partial load (in acc. with EN 303)
(related to net/ gross calorific value)
%
107,0/96,4
•
Normal degree of efficiency (in accordance with DIN 4702 Part 8)
40/30 °C
%
109,4/98,6
(related to net/gross calorific value)
75/60 °C
%
106,1/95,6
•
Standby losses at 70 °C
Watt
95
•
Norm emission factors
Nitrogen oxide NOx
mg/kWh
18
Carbon monoxide CO
mg/kWh
27
• CO
2
content in flue gas max./min. output
%
9,0/8,8
• Dimensions:
see table of dimensions
•
Connections
Flow/Return
Inches
Rp 1¼″
Gas
Inches
R ¾″
Flue gas/combustion air (concentrically)
mm
C100/150
•
Gas flow pressure minimum/maximum
Natural gas E/LL
mbar
18-50
Propane gas (LPG)
mbar
37-50
•
Gas connection value at 0 °C / 1013 mbar:
Natural gas E - (Wo = 15,0 kWh/m
3
) Hu = 9,97 kWh/m
3
m
3
/h
1,65-7,5
Propane gas
3
(H
u
= 25,9 kWh/m
3
)
m
3
/h
0,77-2,90
• Operation voltage
V/Hz
230/50
• Control voltage
V/Hz
24/50
•
Minimum/maximum electrical power consumption
Watt
23/130
• Standby
Watt
7
•
Protection rating
IP
20
• Total sound power level
dB(A)
63
•
Sound pressure level (depending on installation conditions)
2
dB(A)
53
•
Condensate quantity (Natural gas) at 40/30 °C
l/h
7,1
•
pH-value of the condensate
ca. 4,2
•
Values for calculation of the chimney
Requirement flue gas system, temperature class
T 120
Flue gas mass flow rate
kg/h
124,5
Flue gas temperature at nominal output and operation at 80/60 °C
°C
79
Flue gas temperature at nominal output and operation at 40/30 °C
°C
49
Total supply pressure for supply air and flue gas conduit
Pa
140
Maximum draught/underpressure at flue gas outlet
Pa
- 50
1
Data related to Hu. The boiler series is tested for EE/H-settings. With a factory setting of the Wobbe coefficient of 15.0 kWH/m
3
operation at a
Wobbe coefficient of 12.0 up to 15.7 kWh/m
3
is possible without new settings.
2
See also notes at Engineering
3
Data related to H
u
Summary of Contents for TopGas 80