COMMISSIONING
5.4
Changing to a different kind of gas
!
WARNING
Changes are only to be carried out by a re-
cognised specialist!
The boiler is set to natural gas H at the factory (Wobbe
factor 15,0 kWh/m
3
).
Changeover from natural gas H to natural gas L
The changeover to a low caloric natural gas is simple.
Only a check or correction of the CO
2
(O2) value at max.
and min. output must be carried out (see 5.3.4).
Changeover from natural gas H to propane liquid gas
Compliance with the special local provisions
(VKF/DVGW/ÖVGW) for operating a boiler on
liquid gas is imperative in each case.
Ensure that the fuel type in the measuring de
-
vice has been set correctly!
The propane liquid gas conversion kit comprises:
- 1 yellow sticker “Changed too the set gas type: Liquid
gas“ for the boiler rating plate
- 1 gas pressure deflector „Liquid gas“
- 1 gas throttle orifice Ø 6,0 mm
A) With an already connected boiler:
- Close the gas shut-off valve
- Place the system deflector in the operating pan el to
“0“
B) Take off the boiler hood.
C) Extract the gas throttle orifice ø 7,6 mm from the
sealing ring between the gas valve and venturi and
replace it with a gas throttle orifice ø 6,0 mm.
Gas throttle orifice ø 6,0
fig. 13
D) Remove the gas pressure deflector „Natural gas“ and
install the new gas pressure deflector „Liquid gas“.
Wire up the gas pressure deflector (AMP connector
at position 1 and 3).
E) Affix the yellow sticker „change to the set gas type:
Liquid gas“ to the boiler rating plate.
F) with boiler already connected:
-
open the gas valve
- place the system deflector to „I“
G)
Adjust fan speed of rotation according to the
list of parameters „Adaptation for Liquid Gas“
(Parameters 35-41).
H) Set the CO
2
(O2)-content according to 4.3.5 at rat ed
and minimum output to CO
2
= 9,9 - 10,2 (O2 = 5,9 -
5,5) Vol.-% (dry).
5.5
Handing over to the user
5.5.1 Instruction the user
Obtain from the user a written confirmation that
- he has received adequate instruction in the correct
operating and maintenance of the system,
- he has received and read the operating and mainte-
nance instructions, plus additional documents concer-
ning the burner, heating controller etc.,
- and is consequently sufficiently familiar with the sys-
tem.
A pre-printed form (in duplicate) for this confirmation is to
be found on last page of these installation instructions.
Also available on request for flow with the boiler are co-
pies of the official description for submission to the super-
visory authorities or for obtaining a permit from the local
technical inspectorate.
The operating instructions and technical information are
always to be kept in the boiler installation room.
5.5.2 Checking the water level
The customer should be informed of the values between
which the movable pointer on the pressure gauge may
alternate. Refilling and bleeding the air from the system
are to be demonstrated.
5.5.3 Maintenance
On hand-over the customer is to be informed that che-
cking and cleaning of the gas firing is to be carried out at
regular intervals – normally at least once per year- by the
licensed installer or the responsible after-sales organisa-
tion. The conclusion of a maintenance agreement is also
important for economical operation in the sense of the
energy-saving laws and by a permanently correct burner
setting avoids complaints with the statutory inspection of
flue gas loss and pollutant emissions.