11
4 213 894 / 01
TECHNICAL INFORMATION
3.5
Control of the boiler
Control elements on the boiler control panel / Basic control G04.4
The basic controller can be upgraded with an RS-OT (G04.4) or a TopTronic
®
E ZE1 heating controller set.
Normally, the user does not need to set the basic controller.
All settings have been made by the installer or the manufacturer.
Function
Mode indication
Parameter Indication
W
ertanzeige
Meaning, Description
Standby-Mode
Normal position,
Start position
current flow temperaturer
no indication
0
=
Standby, no heat demand, waiting time main gasvalve
1
= Rinsing
2
=
Ignition
3
=
Burner „on“ in heating operation
4
=
Burner „on“ in hot water operation
5
= Air pressure deflector defectiv (no air pressure deflector in
use)
6
= Burner „off“ in heating operation (flow-Temp > flow-temp set point + blockage Offset ZH)
7
= Pump after-run time in heating operation
8
= Pump after-run time in hot water operation
9
= Burner „off“ on hot water operation (flow-Temp > flow-temp. set point + Par.1
(2AB))
Fr
= Frost protection is activated
Su
= Summer short operation is activated
Display: temperature
Changing of
the values
Display: Mode
RESET
Fault-clearance (display is blin-
king, if there is a failure)
Saving of the set
-
tings
Options, to change settings
(Parmeter) (p.ex. Calorifier
temperature)
ON/OFF
Manometer
Function options (stepwise dis-
play option)