4 205 254 / 03
Installation
Installation examples
3.5.3
for room-air-dependent operation
Single flue gas pipes can be shortened to the
•
necessary length but must however be cleanly de-
burred before the assembly, to prevent damage to
the seal in the counter-piece.
When installing the pipes in a shaft, spacer ele-
•
ments must be mounted every 2 m. For the vertical
supporting of the chimney pipeline, the very bot-
tom element must be permanently fixed (mounting
rail or pipe clip).
Horizontal connections must have a gradient of at
•
least 5 cm per running metre in the direction of the
boiler, to permit unobstructed flow of the conden-
sate to the boiler. The complete flue gas system
must be installed to prevent the accumulation of
condensate.
Falls erforderlich ist
ein Inspektions-T-
Stück einzusetzen
Verbrennungsluft
TopGas
If necessary, an inspection
T-piece has to be inserted
Combustion air