Technical details

Adjustable parameters

2.6 

Parameter 7 (2AH) – Set point DHW charging temperature –
Using this parameter the reference value for the DHW temperature can be set where there is no room con-
trol unit or other regulatory device installed. If a reference value is transmitted via an OT bus, the latter (value 
via OT) will always override this parameter. 

Parameter 8 (2AI) – Pump after-run time (DHW) –
During the time which can be set using this parameter the pump continues to run after a phase of hot water 
demand. The after-run time occurs before a switchover to heating operation as well as before a switchover 
to to stand-by mode (to be set at the RS-OT or control unit) or when the firing device is switched OFF. It 
also occurs of course when the desired DHW value has been reached and further heating operation is not 
required.

Parameter 9 (2AJ) – Legionella protection time –
The boiler is periodically heated to the temperature defined using parameter 2AF for the time period which 
can be set using this parameter for protection against legionella infestation. If the parameter value is set to 
0 the legionella protection function is deactivated. 

Parameter 10 (2AK) – Maximum fan speed in DHW mode –
The parameter defines the maximum rpm value for the fan during DHW operation.

Parameter 18 (2BH)
– Maximum heating temperature (when minimum outside temperature has been reached) –
The value which can be set here determines the flow temperature which is to be achieved when the out-
side temperature falls below the value set using parameter 19 (2BI) (minimum outside temperature). (see 
diagram 2). If the OT bus sends a reference value to the firing device, this value is limited by the value set 
using parameter 18. 

Parameter 19 (2BI) - Minimum outside temperature - 19 (2BI) – Minimum outside temperature –
This parameter defines the minimum outside temperature which marks the limit where the flow temperature 
target is to be set at the temperature given by parameter 18 (2BH).

Parameter 20 (2BJ)
– Minimum heating temperature (when maximum outside temperature has been reached) –
If the outside temperature sensor registers the value set using parameter 21 (2BK), then the system targets 
the minimum heating temperature set using this parameter. If the outside temperature exceeds the param-
eter value, the heating demand is cancelled.

Parameter 21 (2BK) – Maximum outside temperature –
If the outside temperature exceeds the values set using this parameter, the heating demand is cancelled. At 
the point where the parameter value is reached the system targets the minimum heating temperature which 
has been set using parameter 20 (2BJ).

Parameter 22 (2BL) –Restart delay following temperature blocking in heating operation mode –
When the boiler is shut down on account of a temperature limit being exceeded, i.e. a set point plus offset, 
the boiler restart is delayed for the period which can be set using this parameter – irrespective of whether 
the hysteresis set for the next heating demand has expired or not.

Parameter 23 (2BM) – Restart delay following heating demand during heating operation –
Immediately following the end of a heating demand phase boiler restarts are delayed. That is to say, if the 
boiler is shut down on account of a reference value trigger being sent from the OT bus to the firing device, a 
restart (triggered by another reference value being reached) is delayed for at least the period of time which 
can be set using this parameter.

Summary of Contents for TopGas 30

Page 1: ...g boiler TopGas 30 35 45 50 60 for natural and liquid gas Wall mounted gas boilers TopGas 30 35 45 50 60 according to DIN 4702 DIN EN 483 and DIN EN 677 are suitable and approved as heat producers for...

Page 2: ...ydraulic connection 15 3 4 1 Protection planning guidelines for the hydraulic connection 15 3 4 2 Boil dry safeguard 15 3 4 3 Gravity brake 15 3 4 4 Minimum flow rate 15 3 4 5 To be provided by custom...

Page 3: ...ng 23 4 3 7 Setting the gas flow rate CO2 O2 and measurement of NOx CO content in the flue gas flue gas measurement 23 4 3 8 Changing to a different kind of gas 24 4 4 Handing over to the user 25 4 4...

Page 4: ...r instructions are enclosed with the individually packed components Adjustment Accessories Further information sources Hoval catalogue Standards regulations Safety instructions 1 4 When working on the...

Page 5: ...on and scale formation in hot water heating systems Firing regulation for the Federal regions DVGW TRGI 86 96 Technical regulations of gas supply enterprises VDE 0100 for electrical installations and...

Page 6: ...R 3 4 R 3 4 R 3 4 R 3 4 Air flue gas mm C80 125 C80 125 C80 125 C80 125 C80 125 Gas flow pressure min max Natural gas E LL mbar 18 50 18 50 18 50 18 50 18 50 Liquid gas mbar 42 57 42 57 42 57 42 57 4...

Page 7: ...on the utilised flue gas pipeline system In the front 500 mm 1 Gas connection R 2 Heating flow Rp 1 3 Heating return Rp 1 4 Condensate drain 32 5 LAS flue gas supply air connection DN 80 125 View fro...

Page 8: ...llective electrode for ignition and flame guide Ionisation Main gas valve ev LPG valve heating room ventilation accessable Water side resistance mbar Flow rate m3 h 0 50 100 150 200 250 300 350 400 45...

Page 9: ...display option Function Mode indication Parameter Indication Value indication Meaning Description Standby Mode Normal position Start position current flow temperature no indication 0 Standby no heat...

Page 10: ...Mode indication Parameter Indication Value indication Meaning Description Informations Mode It is possible to read monetary values from here Point is blinking 0 e g 45 Current flow temperature Heatin...

Page 11: ...sends a reference value to the firing device this value is limited by the value set using parameter 18 Parameter 19 2BI Minimum outside temperature 19 2BI Minimum outside temperature This parameter d...

Page 12: ...s valve or a combustion chamber ventilator is installed Parameter 62 2GG DHW charging switch pump This parameter is used to indicate whether a separate pump is present for DHW charging or there is sim...

Page 13: ...pipeline system Diaphragm expansion tank 3 1 1 Depending on the hydraulic situation of the system an adequately dimensioned diaphragm expansion tank with an inlet pressure of at least 0 3 bar above th...

Page 14: ...ng window 2 Fan 3 Flue gas air inlet 4 Water pressure deflector 5 Flue gas temperature sensor 6 Flow temperature sensor 7 Return temperature sensor 8 Ignition ionisation electrode 9 Heat exchanger 10...

Page 15: ...umen tation When modernising an old heating system with an open expansion tank this is to be converted to a closed heating system with a diaphragm expansion tank and safety valve Protection planning g...

Page 16: ...pe Sie haben die M glichkeit ein neues Shape zu nehmen hovhovalhovalhoval hovalhovalhovalhov P TopGas 30 60 PLP ZUP M 5 T T DKP T T DKP T T SLP Dies ist ein unerlaubter Weg Gehen Sie einen Schritt zur...

Page 17: ...the flue gas extrac tion with heat output gas boilers Waste gas pipelines in compliance 3 5 1 with building construction law The flue gases from the Hoval TopGas 30 35 45 50 60 can be removed via a ga...

Page 18: ...For the vertical supporting of the chimney pipeline the very bot tom element must be permanently fixed mounting rail or pipe clip Horizontal connections must have a gradient of at least 5 cm per runni...

Page 19: ...rennungsluft If necessary an inspection T piece has to be inserted Combustion air TopGas Falls erforderlich ist ein Inspektions T St ck einzusetzen Verbrennungsluft If necessary an inspection T piece...

Page 20: ...ulations of gas supply enterprises should be observed A manually operated shut off device gas shut off cock in accordance with the local regulations is to be installed directly before the boiler Pleas...

Page 21: ...are to be complied with for the electrical installation and com missioning Automatic firing units are safety devices and are not to be opened Boiler control 3 6 3 electrical connection diagram The el...

Page 22: ...f the heati ng surfaces the values given in the table 1 should not be ex ceeded dependent on boil er performance ratings for multi boiler plants rating of smallest boiler ap plies and on the water con...

Page 23: ...be checked during measuring at the boiler site Bleeding the gas pipeline 4 3 3 Open the gas shut off value and bleed the air from the pipeline up to the gas fitting comply with the relevant regulatio...

Page 24: ...eration calorific value HuB is needed Ask your gas utility for it The setting value is calculated as followed Heat load NB Setting value Operation Calorific value HuB kW m3 NB x 1000 l HuB 60 min The...

Page 25: ...urner heating controller etc and is consequently sufficiently familiar with the system A pre printed form in duplicate for this confirma tion is to be found on last page of these installation instruct...

Page 26: ...move the front boiler panel open the control flap lid push the front cover upwards and pull out Unscrew the threaded of the supply pipeline to the gas solenoid valve picture 6 4 1 see next page Detach...

Page 27: ...27 4 205 254 03 Maintenance Picture 6 4 1 Picture 6 4 2 Gas screw connection Bolting Burner plate Picture 6 4 3...

Page 28: ...If the defined gradient limiting curve parameter 15 2BE is exceeded a blocking is caused Before the blocking occurs the speed is minimised There is also a limiting curve existing parameter 16 2BF P 26...

Page 29: ...gher than 100 C by the return sensor occurs a locking E 06 Return sensor interruption If the temperature is lower than 20 C the return sensor seems as disconnected and responds with a lock ing E 07 Fl...

Page 30: ...Internal fault in the automatic firing unit E 17 Flow Return 45K f r 10 Sek If the difference between the flow temperature and return temperature is higher than 45K for more than 10 seconds during a h...

Page 31: ...eating operation 1 C OEM 10 13 P2BC proportional value in heating operation mode 1 C OEM 15 14 P2BD integration time in heating operation mode 1s OEM 20 15 P2BE maximum gradient for flow temperature b...

Page 32: ...2 1 OEM 36 50 P2FE interval 3 1s OEM 30 51 P2FF maximum output during interval 3 1 OEM 52 52 P2FG interval 4 1s OEM 30 53 P2FH maximum output during interval 4 1 OEM 68 54 P2FI interval 5 1s OEM 30 55...

Page 33: ...33 4 205 254 03...

Page 34: ...tallation Place Date Installation address Type Ser No Year of manufacture System installer System user Copy for plant user C O N F I R M AT I O N The user owner of the system herewith confirms that he...

Reviews: