ATROMATIC control system complete with output section and cooled 3-pole soft-starter;
user-friendly and clearly laid out with multilingual touchscreen display; main switch on/off,
assembled ready for operation with the standard modules for monitoring when the mains
power is switched off
User manual with installation instructions
Our ATROMATIC control unit is equipped with a remote monitoring system via the Internet.
The remote monitoring system can be individually adapted depending on the communication
network available. Optionally, all available additional functions in the ATROMATIC control unit
can be retrofitted later.
The electrical and thermal output levels offered by the Hoval combined heat and power plants
can be both manually and automatically adapted to meet individual energy requirements.
In particular, the heat demand can be adapted to the seasonal variations, thereby guaranteeing
low standstill times with optimum electricity yield, and also offering ease of maintenance.
The combined heat and power plants are assembled ready for operation and are subject to a
thorough quality test (approx. 30 hours) prior to delivery. After the test run has been completed
successfully, there is a final inspection including an acceptance report.
Depending on the local conditions of the customer, our combined heat and power plants can be
dismantled into smaller subassemblies, then assembled and filled at the customer’s premises.
All of the following performance and efficiency information is based on a return temperature of
35 °C, the use of optional equipment and natural gas operation (calorific value Hi = 8.8 kWh/m³
under normal conditions). The values relate to a relative air humidity of 30 %, an air pressure
of 1013.25 mbar, a room temperature of 30 °C at a room height of 1.5 m and an intake
air temperature of 25 °C. Deviations are possible if there is a different gas quality and other
air values.
The technical data are listed for standard reference conditions in accordance with ISO 3046-1
(DIN 6271) with a tolerance of +/- 5 %.