6.7.3. Allowed power (menu structure 2.6.11)
1.
Shows the current setting of the allowed power, in this case "Curve". The CHP plant
automatically regulates according to the heating circuit return temperature. The
allowed power can also be changed to "Manual". This setting is for service purposes
only.
2.
Shows the settings of a possible ripple control receiver, which is used for a current-
controlled operation mode of the CHP plant by e.g. an energy supplier or network
operator.
3.
Shows the settings of an input signal, e.g. from a balance point control unit, for a
current-optimised mode of operation of the CHP plant by the owner.
4.
It is possible to delay the switching off of the CHP plant by the external allowed
power setting. The value can be set from 1 to 60000 [s].
5.
These settings determine the response behaviour of the gas choke.
CAUTION:
The values in point 5 are only allowed to be changed by the manufacturer or
a service technician with the agreement of the manufacturer!
Figure 51: Menu - Allowed power