5 Design example
Notice
Use the 'HK-Select' program to design Hoval Indoor Climate Systems.
You can download it free of charge on the Internet.
Design data
Example
■
Geometry of the room
■
Fabric heat losses
■
Room temperature
■
Extract air temperature
■
Comfort requirements (acoustic)
Geometry ..................................50 × 70 × 12 m
Fabric heat losses .....................350 kW
Room temperature ....................20 °C
Extract air temperature..............22 °C
Comfort requirements ...............Standard
Comfort requirements
Define the fan speed in accordance with the acoustic requirements:
■
Low noise level
→
Fan speed 1
■
Normal noise level
→
Fan speed 2
Standard
→
Fan speed 2
Mounting height
■
Calculate the actual mounting height (= distance between the floor and the bottom edge of
the units).
H = Hall height – distance from ceiling – unit height
■
Compare the actual mounting height with the minimum and maximum mounting height
DGV-6/30
→
OK
DGV-6/60
→
OK
DGV-9/60
→
OK
Minimum number of units
■
Determine the minimum number of units for each unit type. Take into account the following criteria:
–
Floor area covered
–
Heat output
–
Unit clearances
Type
Required number
Minimum number
of units
Floor area covered
Heat output
Unit clearances
DGV-6/30
7
12
12
12
DGV-6/60
6
6
6
6
DGV-9/60
5
6
6
6
■
Choose the final solution from the remaining possibilities, depending on the geometry of the hall and the costs.
B
13
TopVent
®
DGV
Design example
Dimensions and weights