3.7 Heat output
Room air temperature
16 °C
20 °C
Unit type
Fan speed
Q
t
S
H
max
Q
t
S
H
max
kW
°C
m
kW
°C
m
DGV-6/30
1
29.2
39.2
8.5
29.2
43.2
8.6
2
29.2
33.2
13.2
29.2
37.2
13.2
DGV-6/60
1
60.5
53.2
8.4
60.5
57.2
8.4
2
60.5
43.7
12.8
60.5
47.7
12.9
DGV-9/60
1
60.5
46.1
8.3
60.5
50.1
8.4
2
60.5
39.9
11.5
60.5
43.9
11.6
Legend:
Q
= Nominal heat output
t
S
= Maximum supply air temperature
H
max
= Maximum mounting height
Reference:
■
At room air temperature 16 °C: extract air temperature 18 °C
■
At room air temperature 20 °C: extract air temperature 22 °C
Table B8: TopVent
®
DGV heat output, supply air temperatures and mounting height
3.8 Minimum and maximum distances
X/2
X
Z
H
Unit type
DGV-6/30
DGV-6/60
DGV-9/60
Fan speed
1
2
1
2
1
2
Unit clearance X
min.
m
10
11
11
12
12
14
max.
m
18
22
21
26
24
29
Mounting height H
min.
m
4.0
4.0
4.0
4.0
5.0
5.0
Distance from ceiling Z
min.
m
0.3
0.3
0.3
0.3
0.4
0.4
Table B9: TopVent
®
DGV minimum and maximum distances
■
1
Allow a free space of 1.5 m for service
and maintenance.
B
11
TopVent
®
DGV
Technical data
Technical data