3.4 Electrical connection
Unit type
GV-3/30
GV-5/50
Supply voltage
V AC
230
230
Permitted voltage tolerance
%
+10 / -15
+10 / -15
Frequency
Hz
50
50
Power consumption
at rated heating capacity
W
250
450
at minimal capacity
W
250
450
in standby mode
W
4
4
Current consumption max.
A
1.1
2.0
Protection rating
–
IP 00B
IP 00B
Table D5: TopVent
®
GV electrical connection
3.5 Gas connection
Unit type
GV-3/30
GV-5/50
Gas appliance type
1)
B
23
, C
13
, C
33
Gas connection
Rp ½ "
(internal)
R ¾"
(external)
Combustion air connection
DN 80
DN 100
Flue gas connection
DN 80
DN 100
Max. length of flue gas duct
2)
9 m
9 m
1) according to method of flue gas evacuation and combustion air supply
2) Equivalent length of formed parts:
– 90° elbow ..... 2 m
– 45° elbow .... 1 m
– 90° T-piece ... 2 m
Table D6: TopVent
®
GV gas circuit connections
3.6 Sound levels
Unit type
GV-3/30 GV-5/50
Sound pressure level (at a distance of 5 m)
1)
dB(A)
49
51
Total sound power level
dB(A)
71
73
Octave sound power level
63 Hz
dB
34
36
125 Hz
dB
47
49
250 Hz
dB
65
67
500 Hz
dB
65
67
1000 Hz
dB
64
66
2000 Hz
dB
64
66
4000 Hz
dB
59
61
8000 Hz
dB
53
55
1) with a hemispherical radiation pattern in a low-reflection room
Table D7: TopVent
®
GV sound power levels
3.7 Heat output
Air entry
temperature
16°C
20 °C
Unit type
Q
t
S
H
max
Q
t
S
H
max
kW
°C
m
kW
°C
m
GV-3/30
29.2
49.0
4.4
29.2
53.0
4.4
GV-5/50
49.9
45.0
5.5
49.9
49.0
5.5
Legend:
Q
= Nominal heat output
t
S
= Maximum supply air temperature
H
max
= Maximum mounting height (with vertical air flow)
Table D8: TopVent
®
GV heat output, supply air temperatures and mounting height