6.3
Electrical connection
6.3.1 General information
A qualified technician must install the electri
-
cal supply to the equipment.
The connection diagram is located in the elec-
trical box of the heat generator; the circuit dia-
gram is supplied separately.
WARNING
The heat generator can only be de-energised
by disconnection from the mains (e.g. all-po-
le switch).
WARNING
All electric power supply circuits must be
switched off before accessing the terminals.
Y
Cable entries
automatic firing device
(return temperature control, chamber emptying system
etc.)
- Ensure that the 230 V power cables and the sensor
cables are routed separately!
- The cable duct is divided into 2 sections for this pur-
pose
Z
Cable infeeds heating controller
(WEZ, etc.)
(Mixer circuit, outdoor sensor etc.)
- Ensure that the 230 V power cables and the sensor
cables are routed separately!
Fig. 39
Y
Z
Figure shows BioLyt (130-160)
Important
!
A main switch must be installed on site in the supply line
which performs an all-poles cut-out and has a clearance
of at least 3 mm between the open contacts.
For Switzerland, the following applies:
For the electrical connection, the circuit diagram
specific
to the plant must be observed!
The electrical connection is to be made in
accordance with the diagram supplied.
Informations:
Fuse protection at least 16A due to the opera-
ting current of the feed unit (suction turbine)!
45
4 214 852 / 01
InSTALLATIOn