4.
Assembly BioLyt (100-160)
4.1
Changing the door attachment side
BioLyt (100-160)
1. Tighten all palm grips (1).
2. Remove screws (2) for the swivel arm top and bot-
tom.
3.
Take off swivel door support (3) and mount on the
opposite side.
4. Swivel the arm (4) to the other side.
5.
Refit screws (2) for the swivel arm top and bottom.
1
2
3
4
Fig. 22
Figure, delivery state
(Boiler door swivel-mounted to the right)
4.2
Water-side and flue-gas side connecti-
on BioLyt (100-160)
•
The boiler can be connected up before fitting the casing
• A return temperature control system is required (see
hydraulic schematics for the individual system)
• A temperature-controlled safety drain valve must be in-
stalled (position of the immersion sleeve (1, Fig. 23).
!
WARNING
• A combined draught-explosion damper
between boiler and flue is mandatory.
• It must be positioned in such a way that
no-one will be injured in the event of de-
flagration.
• The combination draught-explosion dam-
per must be positioned within the boiler
room.
1
Fig. 23
22
4 214 852 / 01
ASSEMBLy BIOLyT (100-160)
Summary of Contents for BioLyt 100
Page 7: ...7 4 214 852 01 NOTES...
Page 21: ...21 4 214 852 01 NOTES...
Page 51: ...51 4 214 852 01...