30
4 205 503 / 14
PARAMETER LISTS
Parameter
Description
Unit
Level
Factory setting
from
gen.
1
1
- UG
(150)
40/41
-
UG
(15)
40/41
-
UG
(20)
40/41
-
UG
(27)
40/41
-
UG
(35)
40/41
-
UG
(50)
41
-
UG
(70)
41
-
UG
(100)
33
2FL 32801 Upward ramp of the fan during operation
min
–1
/s OEM
100
34
2FM 32802 Downward ramp of the fan during operation min
–1
/s OEM
100
35
2FN 32803 Post-venting of the fan after lock-out
sec
OEM
180
36
2FO 32804 Fan speed after a normal switch-off or after
lock-out/blocking
min
–1
OEM
1200 1000
1300
1100 1100 1200 1200 1700
37
2FR 32805 Fan afterrun time after operation or blocking min
OEM
3
38
2FU 32806 Fan speed at boiler freeze protection
min
–1
OEM
1500
39
2GA
32807 Waiting time after opening main gas valve
or activation of heating room fan
min
OEM
0
40
2GB
32808 External main gas valve/ heating room fan
available
OEM
ON
41
2HA 32809 Afterrun heating pump or shut-off valve
min
HF
5
42
2HD 32810 Summer operation (“summer kick”)
sec
OEM
10
43
2IA
32811 Ignition (0-> Internal, 1-> In External,
2-> External)
OEM
2
44
2KM 32812 Step modulation (0-> off, 1->increasing, 2->
increasing and decreasing)
HF
1
45
2LA 32813 Effect of the fault relay
HF
2
46
2NA 32814 ADC/4 value at 0 bar
OEM
25
47
2NB 32815
ADC/4 value at 6 bar and BIC 960 V.2
OEM
145
ADC/4 value at 10 bar and BIC 960 V.3
OEM
225
48
2IB
32816 Extended external ignition time
sec
OEM
8
1
1
1
1
1
1
1
49
2QA 32817 Reserve
%
OEM
70
Adaptations for liquid gas
27
2FF
32795 Fan speed during the first period of pre-
venting
min
–1
OEM
5500
4300
5800 5100 6100
6300
4900 6100
28
2FG
32796 Fan speed at start
min
–1
OEM
3300 3500
2500 2500
3000 3000
2500
3000
29
2FH 32797 Maximum fan speed
min
–1
OEM
5500
4300
5800 5100 6100
6300
4900 6100
30
2FI
32798 Minimum fan speed
min
–1
OEM
1600 1400 1500 1400
1300
1400 1400 1500
36
2FO 32804 Fan speed after a normal switch-off or after
lock-out/blocking
min
–1
OEM
1600 1400 1500 1400
1300
1400 1400 1700