38
4 205 503 / 14
PARAMETER LISTS
Parameter
Description
Unit
Level
Factory setting
from
gen.
1
1
- UG
(150)
11/20/21/30/31/41
-
UG
(450)
11/20/21/30/31/41
-
UG
(500)
11/20/21/30/31/41
-
UG
(575)
11/20/21/30/31/41
-
UG
(650)
11/20/21/30/31/41
-
UG
(720)
21/30/
41
-
UG
(850)
21/30/
41
-
UG
(1000)
33 2FL 32801 Upward ramp of the fan during operation
min
–1
/s OEM
100
34 2FM 32802 Downward ramp of the fan during operation
min
–1
/s OEM
100
35 2FN 32803 Post-venting of the fan after lock-out
sec OEM
180
36 2FO 32804 Fan speed after a normal switch-off or after lock-out/
blocking
min
–1
OEM
1200 900 900 1000 1000 1000 900 1200
37 2FR 32805 Fan afterrun time after operation or blocking
min OEM
3
38 2FU 32806 Fan speed at boiler freeze protection
min
–1
OEM
1500
39
2GA
32807 Waiting time after opening main gas valve or activation
of heating room fan
min OEM
0
40 2GB
32808 External main gas valve/ heating room fan available
OEM
ON
41
2HA 32809 Afterrun heating pump or shut-off valve
min
HF
5
42
2HD 32810 Summer operation (“summer kick”)
sec OEM
10
43
2IA
32811 Ignition (0-> Internal, 1-> In External, 2-> External)
OEM
2
44
2KM 32812 Step modulation
(0-> off, 1->increasing, 2-> increasing and decreasing)
HF
1
45
2LA 32813 Effect of the fault relay
HF
2
46
2NA 32814 ADC/4 value at 0 bar
OEM
25
47
2NB 32815
ADC/4 value at 6 bar and BIC 960 V.2
OEM
145
ADC/4 value at 10 bar and BIC 960 V.3
OEM
225
48 2IB
32816 Extended external ignition time
sec OEM
8
1
1
1
1
1
1
1
49
2QA 32817 Reserve
%
OEM
70
Adaptations for liquid gas
27 2FF
32795 Fan speed during the first period of pre-venting
min
–1
OEM
5500
3700
4100
3900
4400 4200 4200 5200
28 2FG
32796 Fan speed at start
min
–1
OEM
3300
1700 1800 1800 1800 2000 1700 1700
29
2FH 32797 Maximum fan speed
min
–1
OEM
5500
3700
4100
3900
4400 4200 4200 5200
30
2FI
32798 Minimum fan speed
min
–1
OEM
1600
1300 1300
1400 1400 1500
1300
1500
36 2FO 32804 Fan speed after a normal switch-off or after lock-out/
blocking
min
–1
OEM
1600
1300 1300
1400 1400 1500
1300
1500