27
4 205 503 / 14
PARAMETER LISTS
13.5 30 - UG (15-90)
Parameter
Description
Unit
Level
Factory setting
from
gen.
1
1
- U
G
(1
50
)
30
-
UG
(15)
30
-
UG
(20)
30
-
UG
(27)
30
-
UG
(35)
30
-
UG
(50)
30
-
UG
(70)
30
-
UG
(90)
30
-
UG
(100)
1
2AA
Blocking temperature
°C
OEM
95
90
90
90
90
90
90
90
90
2
2AC
Maximum reference value
°C
BE
80
3
2AD Switch-off hysteresis above reference value
°C
OEM
10
5
5
5
5
5
5
5
5
4
2AE
Switch-on difference relating to tripping point
°C
HF
10
5
2AF
Proportional part
°C
OEM
40
10
10
10
10
10
10
10
10
6
2AG
Integral part
sec
OEM
100
180
180
180
180
180
180
180
180
7
2AH Differential part
sec
OEM
25
10
10
10
10
10
10
10
10
8
2AI
Reference value when bus interruption
°C
HF
75
9
2AJ Max. temperature rise at low flow
temperature
°C/s
OEM
1
10
2AK Max. temperature rise at high flow
temperature
°C/s
OEM
0.5
11
2AL “Low” flow temperature
°C
OEM
60
12
2AM “High” flow temperature
°C
OEM
80
13
2BC
Lock-out flue gas temperature
°C
OEM
110
14
2BD Blocking flue gas temperature
°C
OEM
100
15
2CA
Gas pressure switch attached
OEM
ON
16
2DA Water pressure sensor attached
OEM
ON
17
2DB Water pressure warning
bar
OEM
1
18
2DC Water pressure hysteresis
bar
OEM
0.2
19
2DD Blocking pressure min.
bar
OEM
0.5
20
2DE Blocking pressure min – hysteresis
bar
OEM
0.2
21
2DF Blocking pressure max
bar
OEM
4.8
2.8
2.8
2.8
2.8
2.8
3.8
3.8
3.8
22
2DG Blocking pressure max – hysteresis
bar
OEM
0.2
23
2DH Lock-out pressure max
bar
OEM
5
3
3
3
3
3
4
4
4
24
2DI Max. boiler performance at pressure warning
%
OEM
50
25
2EC
Ionisation warning
µA
OEM
3
26
2FA
Number of hall impulses per revolution
OEM
3
2
2
2
2
2
2
2
2
27
2FF
Fan speed during the first period of pre-
venting
min
–1
OEM
5700 5000
6300
5500 6500 6800 5200 6200
6300
28
2FG
Fan speed at start
min
–1
OEM
1900
3500
2500 2200 2500 2500 2100 2500 2700
29
2FH Maximum fan speed
min
–1
OEM
5700 5000
6300
5500 6500 6800 5200 6200
6300
30
2FI
Minimum fan speed
min
–1
OEM
1200 1000
1300
1100 1100 1200 1200
1300 1300
31
2FJ Upward ramp of the fan during venting
min
–1
/s OEM
500
32
2FK Downward ramp of the fan during venting
min
–1
/s OEM
200