39
4 205 503 / 14
PARAMETER LISTS
Parameter
Description
Unit
Level
Factory setting
1
- CompactGas
®
(240)
1
- CompactGas
®
(200)
1
- CompactGas
®
(280)
1 2AA
Blocking temperature
°C
OEM
100 100 100
2 2AC
Maximum reference value
°C
BE
85
85
85
3 2AD Switch-off hysteresis above reference value
°C
OEM
10
4 2AE
Switch-on difference relating to tripping point
°C
HF
10
5 2AF
Proportional part
°C
OEM
20
20
20
6 2AG
Integral part
sec OEM
100 100 100
7
2AH Differential part
sec OEM
0
0
0
8 2AI
Reference value when bus interruption
°C
HF
75
9
2AJ Max. temperature rise at low flow temperature
°C/sec OEM
2
2
2
10
2AK Max. temperature rise at high flow temperature
°C/sec OEM
1
1
1
11
2AL “Low” flow temperature
°C
OEM
60
12
2AM “High” flow temperature
°C
OEM
80
13
2BC
Lock-out flue gas temperature
°C
OEM
110
14
2BD Blocking flue gas temperature
°C
OEM
100
15 2CA
Gas pressure switch attached
OEM
ON
16
2DA Water pressure sensor attached
OEM
ON
17
2DB Water pressure warning
bar OEM
1
18
2DC Water pressure hysteresis
bar OEM
0.2
19
2DD Blocking pressure min.
bar OEM
0.5
20
2DE Blocking pressure min – hysteresis
bar OEM
0.2
21
2DF Blocking pressure max
bar OEM
4.8
22
2DG Blocking pressure max – hysteresis
bar OEM
0.2
23 2DH Lock-out pressure max
bar OEM
5
24
2DI Max. boiler performance at pressure warning
%
OEM
50
25 2EC
Ionisation warning
µA
OEM
3
13.11 1 - CompactGas
®
(200-280)
Attention:
The automatic gas firing device BIC 960 which must be used for the CompactGas
®
boiler does not correspond with the
BIC 960 used with the UltraGas
®
boiler.
Therefore when exchanging an automatic gas firing device on a CompactGas
®
, an article No. 6017 963 must be
installed in the ordered BIC 960.
Otherwise the locking fault E:02 would be displayed which cannot be acknowledged because no flue gas sensor is
installed in the CompactGas
®
.
Blocking temperature to max. 100°C on request.