G. Installation of Remote Condenser Unit

   WARNING

1. Installation of remote condenser unit must be 

performed by properly trained and certifi ed service 
personnel.

2. Failure to install the equipment within these 

guidelines may adversely aff ect safety, performance, 
component life, and warranty coverage.

1. Checks Before Installation

1) Remove the shipping carton, tape, and packing 

material.

2) Check that the refrigerant lines do not rub or touch lines 

or other surfaces, and that the fan blades move freely.

2. Loction

CAUTION

1. The remote condenser unit is intended for outdoor 

use. Normal operating ambient temperature should 
be within -29°C to +50°C. Operation of the remote 
condenser unit, for extended periods, outside of 
this normal temperature range may aff ect icemaker 
performance.

2. The maximum line length for the standard 

refrigerant charge is 20 m. With additional 
refrigerant, the maximum line length is 30.5 m. For 
details, see "II.G.5. Line Set Exceeding 20 m."

3. The maximum vertical distance between the remote 

condenser unit and the icemaker is 10 m above 
or 3 m below the icemaker. These distances are 
measured fi tting to fi tting. See Fig. 8.

Fig. 8

Icemaker 

Remote 

Condenser 

Unit 

Service 

Loop

Max. 

10 m

The remote condenser unit must be positioned in a 
permanent site under the following guidelines:

• A fi rm and fl at site.

• A dry and well ventilated area with 61 cm clearance in 

both front and rear for proper air circulation and ease 
of maintenance and/or service should they be required. 
See Fig. 9.

3. Setup

1) Secure the legs to the remote condenser unit with the 

8 bolts and nuts provided. See Fig. 10.

2) The legs have 8 mounting holes. Secure the legs to 

the permanent site with 8 bolts (not included).

Fig. 9

Min. 61 cm Clearance

Air

Air

 Fig. 10

Bolts with Split 

Lock Washer 

and 

Flat Washer

Nuts

4. Line Set

CAUTION

1. The icemaker, line set, and remote condenser unit 

must contain the same type of refrigerant. Mixing 
of refrigerants will result in improper operation and 
possible damage to the refrigeration system.

2. The maximum line length for the standard 

refrigerant charge is 20 m. With additional 
refrigerant, the maximum line length is  30.5 m. 
For details, see "II.G.5. Line Set Exceeding 20 m."

1) Route a 1/2" OD copper tube discharge line and a 

3/8" OD copper tube liquid line between the remote 
condenser unit and the icemaker. Leave a service 
loop behind the icemaker to allow the icemaker to be 
pulled out for service. See Fig. 11.

CAUTION

1. Ensure that there are no traps and no kinks in the 

line set.

2. Do not coil extra line set. Fabricate the line set to 

the proper length.

2) Insulate the two copper tubes separately. 

3) Install Parker quick connect couplings on each 

end.  OS-QUICK, an optional Hoshizaki universal 

quick connect coupling kit, is recommended. 

CAUTION! Before brazing, remove the Schrader 

valve core from the access port. When brazing, 

protect the coupling by using a wet cloth to 
prevent the coupling from overheating. 

4) Allow the coupling to cool, then replace the Schrader   

valve core.

Summary of Contents for KM-590DJ

Page 1: ...KM 590DJ L1F137101 031619 No 15 Qingqiu Street Suzhou Industrial Park Suzhou 215126 China INSTRUCTION MANUAL STACKABLE CRESCENT CUBER ...

Page 2: ...nd Drain Connections 15 I Final Checklist 18 J Startup 19 III Cleaning and Maintenance Instructions 19 A Cleaning and Sanitizing Instructions 19 B Maintenance 20 C Preparing the Icemaker for Long Storage 21 IV Warranty 21 V Disposal 21 IMPORTANT This manual should be read carefully before the appliance is installed and operated Read the warnings and guidelines contained in this manual carefully as...

Page 3: ...lled in accordance with applicable national state and local codes and regulations Electrical connection must be hard wired and must meet national state and local electrical code requirements Failure to meet these code requirements could result in death electric shock serious injury fire or damage The icemaker requires an independent power supply of proper capacity See the nameplate for electrical s...

Page 4: ...uting conduit and disconnect if required must meet national state and local electrical code requirements Failure to meet these code requirements could result in death electric shock serious injury fire or damage NOTICE Follow the water supply drain connection and maintenance instructions carefully to reduce the risk of costly water damage In areas where water damage is a concern install in a contai...

Page 5: ...hout prior notice 1 KM 590DJ Model KM 590DJ Type Air cooled crescent cube ice Power Supply 1 phase 200 240V 50Hz Electric Consumption 2080W AT 32 C WT 21 C Ice Production per 24h 590kg AT 10 C WT 10 C Dimensions 1220mm W x 695mm D x 695mm H Refrigerant R404A 1 90kg GWP 3920 CO2 7 488t Insulation Foam Blowing Agent Cyclopentane Weight Net 136kg Gross 154kg Ambient Temp 7 38 C Water Supply Temp 7 32...

Page 6: ...CE KM 590DJ Allow 15 cm clearance at rear sides and top for proper air circulation and ease of maintenance and or service should they be required The ice storage bin opening must match the bottom opening as in the illustration Units mm Rear Side Bottom ...

Page 7: ...ENGLISH 5 Intentionally Left Blank ...

Page 8: ...ENGLISH 6 Intentionally Left Blank ...

Page 9: ...mediately report any damage to the carrier Upon opening the container any concealed damage should also be immediately reported to the carrier Remove the shipping carton tape and packing material If any are left in the icemaker it will not work properly WARNING Keep packing material plastic bags and expanded polystyrene away from children Remove the panels to prevent damage when installing the icem...

Page 10: ...hole in the bottom of the icemaker Route the cable through the bushing in the bin control cable bracket then secure the bracket Leave as little slack as possible inside the storage bin Route the cable through the wire saddles e Connect the bin control cable connector to wire harness connector A coming from the control box Note 1 Wire harness has one connector to plug into the bin control cable and...

Page 11: ...r unit s bin control assembly in its original position It will not be used 8 Route lower unit wire harness connector B through the hole in the bottom of the upper unit Route the wiring through the bushing in the bin control cable bracket then through the wire saddles 9 Connect lower unit wire harness connector B to upper unit wire harness connector A Note Wire harness is connected to the control b...

Page 12: ...lue wire must be connected to the neutral conductor of the power source See Fig 7 CAUTION Miswiring may result in severe damage to the icemaker Neutral N Line L Ground Earth LBu BR GR Y Junction Box 7 8 22 2 mm Diameter Opening The opening for the power supply connection is 7 8 22 2 mm DIA to fit a 1 2 trade size conduit If a power cord is used to provide electricity to the icemaker in place of a h...

Page 13: ...ar for proper air circulation and ease of maintenance and or service should they be required See Fig 9 3 Setup 1 Secure the legs to the remote condenser unit with the 8 bolts and nuts provided See Fig 10 2 The legs have 8 mounting holes Secure the legs to the permanent site with 8 bolts not included Fig 9 Min 61 cm Clearance Air Air Fig 10 Bolts with Split Lock Washer and Flat Washer Nuts 4 Line S...

Page 14: ...point the nut has covered most of the threads on the male fitting e Mark a reference line on the female coupling and the remote condenser unit or icemaker panel Using a backup wrench on the back of the female coupling tighten the six sided nut of the female coupling an additional 1 6 turn See Fig 13 8 If the line set exceeds 20 m see II G 5 Line Set Exceeding 20 m for proper charging of the unit 5 ...

Page 15: ... air cooled models the icemaker should have power for a minimum of 4 hours prior to startup to prevent compressor damage Fig 14 Wire Color Code BR brown GR Y green and yellow V violet W white Usually an electrical permit and services of a licensed electrician are required The opening for the power supply connection is 7 8 22 mm DIA to fit a 1 2 trade size conduit 1 Remove the louver panel 2 Remove ...

Page 16: ...e upper remote condenser unit on top of the lower See Fig 15 3 Secure the upper remote condenser unit to the lower remote condenser unit with the 4 screws provided 4 Install refrigerant lines and make electrical connection as described earlier in this section Fig 15 Upper Remote Condenser Unit Screws Lower Remote Condenser Unit Screws ...

Page 17: ...ir temperature is going to go below 0 C For details see III C Preparing the Icemaker for Long Storage A plumbing permit and services of a licensed plumber may be required in some areas External filters strainers or softeners may be required depending on water quality Contact your local Hoshizaki distributor for recommendations The icemaker and condensation drain line s storage bin drain line and wa...

Page 18: ... 5 cm air gap Floor Drain Icemaker Drain Outlet 3 4 FPT Bin Condenser Water Supply Line Shut Off Valve Condenser Water Supply Line Drain Valve Condenser Water Supply Inlet 1 2 FPT Condenser Drain Outlet 3 8 FPT Minimum 3 8 10 mm Nominal Copper Water Tubing Vent Tube Vent Tube Minimum 3 4 18 mm Nominal Hard Pipe Minimum 3 8 10 mm Nominal Hard Pipe Minimum 3 8 10 mm Nominal Copper Water Tubing Bin Dr...

Page 19: ...ker Icemaker Water Supply Inlet 1 2 FPT 5 cm air gap Floor Drain Icemaker Drain Outlet 3 4 FPT Bin Condenser Water Supply Line Shut Off Valve Condenser Water Supply Line Drain Valve Condenser Water Supply Inlet 1 2 FPT Condensation Drain Outlet 3 8 9 5 mm OD Hard Tube Minimum 3 8 10 mm Nominal Copper Water Tubing Vent Tube Vent Tube Minimum 3 4 18 mm Nominal Hard Pipe Minimum 3 8 10 mm Nominal Copp...

Page 20: ...roper ground earth also been installed to the remote condenser unit 8 Are the water supply line shut off valves and drain valves installed Has the water supply pressure been checked to ensure a minimum of 0 07MPa 0 7 bar and a maximum of 0 78MPa 7 8 bar Note The icemaker may stop running when the water supply is off or if the pressure is below 0 07MPa 0 7 bar When the proper water pressure is reache...

Page 21: ...ntation and labels provided with the icemaker Consult with your local distributor about cleaning and maintenance service To obtain the name and phone number of your local distributor contact your nearest Hoshizaki Service office WARNING 1 Except as specified below only qualified service technicians should attempt to service this icemaker 2 CHOKING HAZARD Ensure all components fasteners and thumbscrews...

Page 22: ... boot in their correct positions Reconnect the vent tube and the flush tube 8 Pour the cleaning solution into the water tank 9 Move the control switch on the control box to the WASH position 10 Replace the insulation panel and the front panel in their correct positions 11 Turn on the power supply to start the washing process 12 Turn off the power supply after 30 minutes 13 Remove the front panel and...

Page 23: ... cooled model remove the water from the water cooled condenser 1 Make sure the power supply is off then remove the front panel and right side panel 2 Close the condenser water supply line shut off valve If connected to a closed loop system also close the condenser return line shut off valve 3 Open the condenser water supply line drain valve If connected to a closed loop system also open the condenser...

Reviews: