2. BRAZING
DANGER
1. Refrigerant R-404A itself is not flammable at atmospheric pressure and
temperatures up to 176° F.
2. Refrigerant R-404A itself is not explosive or poisonous. However,
when exposed to high temperatures (open flames) R-404A can be
decomposed to form hydrofluoric acid and carbonyl fluoride both of
which are hazardous.
3. Always recover the refrigerant and store it in an approved container. Do
not discharge the refrigerant into the atmosphere.
4. Do not use silver alloy or copper alloy containing Arsenic.
5. Do not use R-404A as a mixture with pressurized air for leak testing.
Refrigerant leaks can be detected by charging the unit with a little
refrigerant, raising the pressure with nitrogen and using an electronic
leak detector.
Note: All brazing-connections inside the bin are clear-paint coated. Sandpaper the
brazing connections before unbrazing the components. Use a good abrasive cloth
to remove coating.
5) Disconnect the Vacuum Pump, and attach a Refrigerant Service Cylinder to the
High-side line. Remember to loosen the connection, and purge the air from the
Hose. See the Nameplate for the required refrigerant charge. Hoshizaki
recommends only virgin refrigerant or reclaimed refrigerant which meets
ARI Standard No. 700-88 be used.
6) A liquid charge is recommended for charging an R-404A system. Invert the service
cylinder. Open the High-side, Service Manifold Valve.
7) Allow the system to charge with liquid until the pressures balance.
8) If necessary, add any remaining charge to the system through the Low-side. Use a
throttling valve or liquid dispensing device to add the remaining liquid charge
through the Low-side access port with the unit running.
9) Close the two Refrigerant Access Valves, and disconnect the Hoses and Service
Manifold.
10) Cap the Access Valves to prevent a possible leak.
Summary of Contents for KM-150BAF
Page 5: ...5 I SPECIFICATIONS 1 KM 150BAF ...
Page 6: ...6 2 KM 150BWF ...
Page 7: ...7 II GENERAL INFORMATION 1 CONSTRUCTION a KM 150BAF ...
Page 8: ...8 b KM 150BWF ...
Page 14: ...14 Control Products HOSHIZAKI001 Board ...
Page 15: ...15 Control Products HOS 001A Board ...
Page 23: ...23 TEST PROGRAM OF ALPINE CONTROLLER BOARD ...
Page 25: ...25 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERANT CIRCUIT a KM 150BAF ...
Page 26: ...26 b KM 150BWF ...
Page 30: ...30 4 PERFORMANCE DATA a KM 150BAF Air cooled ...
Page 31: ...31 b KM 150BWF Water cooled ...