2
[k] CANCELING SOFT START
To cancel the “soft start” (3 minute delay), turn on the power supply while pressing the Set
Point Button. The Compressor and Condenser Fan Motor will start at the same time after
0 seconds.
When the soft start is cancelled, the illuminated seven segment LED on the Temperature
Display Window changes to the model setting number. To resume the cabinet temperature
display, press the Set Point Button again or wait for 30 seconds.
Note: If the power supply is turned off while the Compressor is running and immediately
turned back on to cancel the soft start, the high-side and low-side pressures cannot
be equalized, often resulting in Compressor starting failure. Do not cancel the soft
start for at least 2.5 minutes after the power supply is turned off.
[l] ERROR CODES
In case of trouble, the Temperature Display Window will alternately flash every second
between one of the following error codes and the cabinet temperature. See “III. 1. ERROR
CODES” for further details.
Code
Error
Code
Error
E1
Cabinet Temperature Too High
E7
Condenser Clogged
E2
Cabinet Temperature Too Low
E8
Defrost Thermistor Defective
E3
Defrost Cycle Too Long
E9
Clog Thermistor Defective
E4
Abnormal High-Side Pressure
EA
EEPROM Write Error
E5
Interior Thermistor Defective
Ed
EEPROM Verify Error
In case of error, an external output (2V DC) function is available for connection with a
buzzer.
[m] CONTROLLER BOARD MODEL SETTING
To indicate the Controller Board model setting number on the Temperature Display
Window, turn on the power supply while pressing the Set Point Button.
Note: Proper model setting is required when the Controller Board is replaced. See “6.
BUTTON OPERATION” for further details.
Summary of Contents for HFE-140B Series
Page 6: ... 2 DIMENSIONS SPECIFICATIONS a HRE 70B ...
Page 7: ... b HRE 140B ...
Page 8: ... c HFE 70B ...
Page 9: ... d HFE 140B ...
Page 10: ... e HRE 70B F ...
Page 11: ... f HRE 140B F ...
Page 12: ... II TECHNICAL INFORMATION 1 WIRING DIAGRAM a HRE 70B ...
Page 13: ...10 b HRE 140B ...
Page 14: ...11 c HFE 70B ...
Page 15: ...12 d HFE 140B ...
Page 16: ...13 e HRE 70B F ...
Page 17: ...14 f HRE 140B F ...
Page 18: ...15 2 REFRIGERATION CIRCUIT Refrigerant HFC 134a HRE series HFC 404A HFE series ...