46
PROBLEM
POSSIBLE CAUSE
REMEDY
c) Gear Motor Relay
1. Coil winding opened.
1. Replace.
2. Bad contacts.
2. Check for continuity and
replace.
d) Control Timer
(Printed Circuit Board)
1. Broken.
1. Replace.
e) Gear Motor Protect
Relay
1. Coil winding opened.
1. Replace.
2. Bad contacts.
Check for continuity and
replace.
[4]
a) Gear Motor Fuse
(BUSSMAN GMD
1.5A)
1. Blown Fuse.
1. See "3. [3] Gear Motor
Protector operates
frequently." Find out the
cause and replace the
Fuse.
b) Thermal Protector
(Gear Motor)
1. Bad contacts.
1. Check for continuity and
replace.
[5] Gear Motor starts,
but Compressor (for
Solenoid Valves) will
not start or operates
intermittently
a) Pressure Switch
1. Dirty Air Filter or
Condenser.
1. Clean.
2. Ambient or condenser
water temperature too
warm.
2. Get cooler.
3. Condenser water
pressure too low or
off. (Water-cooled
model only)
3. Check and get
recommended pressure.
4. Water Regulating
Valve set too high.
(Water-cooled model
only)
4. Adjust it lower.
5. Fan not rotating.
5. See "3. [1] a) Fan Motor."
6. Refrigerant
overcharged.
6. Recharge.
7. Refrigerant line or
components plugged.
7. Clean and replace drier.
8. Bad contacts.
8. Check for continuity and
replace.
9. Loose connections.
9. Tighten.
b)
1. Bad contacts.
1. Replace. Check for
continuity and replace.
2. Coil winding opened.
2. Replace Timer.
c) Starter
1. Bad contacts.
1. Check for continuity and
replace.
2. Coil winding opened.
2. Replace.
3. Loose Connections.
3. Tighten.
d) Start Capacitor or Run
Capacitor
1. Defective.
1. Replace.
Water has been
supplied, Fan Motor
starts, but Gear
Motor and
Compressor will not
start.
X2 Relay on Control
Timer
Summary of Contents for F-1500MA-C
Page 11: ...11 2 Condenser Unit URC 12F...
Page 18: ...18 III Technical Information 1 Water Circuit and Refrigeration Circuit F 1500MAH C...
Page 19: ...19 F 1500MWH C...
Page 20: ...20 F 1500MRH C...
Page 21: ...21 2 Wiring Diagrams F 1500MAH C...
Page 22: ...22 F 1500MWH C...
Page 23: ...23 F 1500MRH C...
Page 25: ...25 b When reservoir has been filled gear motor starts immediately...
Page 26: ...26 c Compressor starts about 60 sec after gear motor starts...
Page 27: ...27 d Bin control operates and about 6 sec later compressor and gear motor stop simultaneously...
Page 28: ...28 e Low water except water cooled model...
Page 32: ...32 4 Timing Chart...
Page 33: ...33...
Page 34: ...34...
Page 35: ...35...
Page 36: ...36...