8

Installation Instructions Kemlan Natural Draft Electronic Ignition Gas Fireplaces

Gas Installation

1.  Check unit is suitable for intended gas supply.

2. 

Note position on gas appliance on drawing specification 

on right hand side of appliance.

3. 

Gas cock has to be fitted prior to gas burner to allow 

unit to be removed for servicing.

4.  If  material  has  been  installed  around  firebox  and 

access panel below is not accessible the top plate can 

be removed to gain access by removing four screws 

and lifting out top plate.

5.  Connection is half inch BSP fitting. Cut and debur both 

ends of pipe. Fit end to gas supply point and turn on 

for approximately 5 seconds to clear dirt and grit out 

of pipe. Connect into gas valve.

6.  Turn on the gas and check all connections for leaks 

using approved method for testing. Fix any leaks.

Adjusting Pressure, Pilot

and Low Fire

1. 

All settings are set to operate at nominal pressure (see 

data  plate).  Test  points  to  measure  inlet  and  outlet 

pressure  are  located  on  gas  valve.  Unscrewbrass 

screw  on  test  point  pressure  nipples  and  attach 

manometer  and  read  pressures  with  unit  running. 

Adjust pressure to data plate requirements.

2. 

Check low fire if adjusted correctly.

3. 

Note:  Failure  to  set  pressures  correctly  will  void 

warranty on the unit.

Lighting Instructions

Natural Draft Electronic Ignition Fireplaces are provided 

with 240 volt electronic ignition systems. 

An on/off wall switch is supplied and fitted with unit. The 

fireplace is switched on from wall switch. Power is then 

sent to valve to light pilot and main burner will then ignite 

from pilot. 

Burner  is  turned  off  by  turning  off  wall  switch.  System 

does not have a high low burner switch.

Laying the fire - Coal & Pebble

• 

Evenly spread a bag of Vermiculite into the burner 

tray. Tray should be completely filled to the top with 

Vermiculite to a depth of approximately 45mm.

• 

Unpack the coals/pebbles contained in a clear plastic 

bag and lay a row of coals/pebbles on the vermiculite 

along the back of the burner tray leaving approximately 

12-15mm between them.

•  Leave spaces at the edges to allow free flow of gas.

•  Place a further row of coals/pebbles directly in front 

of the first row but staggered so that the second row 

of coals are behind the gaps of the first row leaving 

approximately  12-15mm  between  the  rows  of  each 

coal/pebble.

•  Lay further rows of staggered coals/pebbles depending 

on the size of the basket grate.

• 

Once the bottom layer is completed, build up 2-3 tiers 

of coals in a honeycomb pattern to form an elongated 

pyramid.

NOTE: only burners of the 700, 800 and 1000 series 

can have multiple layers of coals/pebbles. The 1400 

and 1800 burners are to have single layer only.

• 

Lay the coals/pebbles so that some irregularity to the 

pile through which the flames may lick, is created.

•  Your  aim  is  to  build  “windows”  into  the  fire  through 

which  the  radiant  effect  may  show  but  at  the  same 

time, not leaving such large gaps between the coals/

pebbles  that  excessive  air  may  enter  and  “damp 

down” the red glow.

•  After the fire has been alight for 15 minutes, you may 

wish to add the odd coal/pebble or even relay the fire 

completely. Allow  to  cool  before  touching  the  coals/

pebbles.

•  Experience  will  enable  you  to  obtain  a  pleasing 

appearance with suitable heat output, but please bear 

in mind that it is important to maintain the general 

pattern described above and indicated in illustrations.

SEE NEXT PAGE FOR COAL & PEBBLE DIAGRAMS

Summary of Contents for 1100 Low Line 1000 Mk2 Pebble

Page 1: ...Installation Instructions Horizon Natural Draft Electronic Ignition Gas Fireplaces ...

Page 2: ...k2 Pebble 1400 Mk2 Coal 2000 Low Line 1800 Mk2 Pebble 1800 Mk2 Coal SINGLE SIDED MODELS 700 Low Line 700 Mk2 Pebble 700 Mk2 Coal 700 Ironbark Log Mk4 850 Low Line 800 Mk2 Pebble 800 Mk2 Coal 850 Ironbark Log Mk4 1100 Low Line 1000 Mk2 Pebble 1000 Mk2 Coal 850 Ironbark Log Mk4 1500 Low Line 1400 Mk2 Pebble 1400 Mk2 Coal 2000 Low Line 1800 Mk2 Pebble 1800 Mk2 Coal CANTILEVER 700 Cantilever 700 Mk2 P...

Page 3: ...Natural Draft Electronic Ignition N D E I flue system shall be installed by authorized personnel in accordance with the manufacturer s installation instructions local gas fitting regulations municipal building codes electrical wiring regulations and any other statutory regulations Contact your local building authorities about restrictions and installation inspections that may be required If in dou...

Page 4: ... 435 900 2246 350 300 OPENING DIMENSIONS 770 870 870 1000 1000 SINGLE SIDED 700 Low Line 850 Low Line 700 270 390 365 A B C1 C 850 270 430 405 670 D 770 1000 E 1095 225 F 275 178 G 225 1100 Low Line 1100 270 430 405 770 1358 275 225 1500 Low Line 1500 290 460 435 900 1746 300 250 2000 Low Line 2000 290 460 435 900 2246 300 250 OPENING DIMENSIONS C1 D D HEIGHT OF FIREBOX UNIT USING HEAT ZONE KIT RE...

Page 5: ...onic Ignition Gas Fireplaces Measurements and Specification of N D E I CANTILEVER Cantilever 700 Cantilever 1100 1190 1266 478 440 A A1 B1 B 1424 1500 478 440 455 C 455 225 D 225 275 D1 275 177 E 177 405 F 405 336 G 336 AGA Approved Cowl to suit flue sizes ...

Page 6: ...2293 490 980 510 including 10mm plasterboard SINGLE SIDED 700 Low Line 850 Low Line 1056 410 750 420 A B C B 1145 450 845 460 1100 Low Line 1408 450 845 460 1500 Low Line 1796 480 950 490 2000 Low Line 2296 480 950 490 including 10mm plasterboard 1050 1145 1145 1280 1280 C C INTERNAL FRAME HEIGHT WHEN USING HEAT ZONE KIT REFER TO HEAT ZONE INSTALL PAGE 1050 1145 1145 1280 1280 C C INTERNAL FRAME H...

Page 7: ...7 Installation Instructions Kemlan Natural Draft Electronic Ignition Gas Fireplaces Section SINGLE SIDED SECTION CANTILEVER SECTION SINGLE SIDED ELEVATION CANTILEVER ELEVATION Elevation ...

Page 8: ...ning off wall switch System does not have a high low burner switch Laying the fire Coal Pebble Evenly spread a bag of Vermiculite into the burner tray Tray should be completely filled to the top with Vermiculite to a depth of approximately 45mm Unpack the coals pebbles contained in a clear plastic bag and lay a row of coals pebbles on the vermiculite along the back of the burner tray leaving appro...

Page 9: ...ireplaces Laying the fire Coal Pebble MARK 2 COALS 700 800 600 x 155 MARK 2 PEBBLES 700 800 600 x 155 MARK 2 COALS 1000 992 x 155 MARK 2 PEBBLES 1000 922 x 135 MARK 2 COALS 1400 1400 x 64 MARK 2 PEBBLES 1400 1400 x 64 MARK 2 COALS 1800 1800 x 64 MARK 2 PEBBLES 1800 1800 x 64 ...

Page 10: ...arge log has two holes on the underside to position in place 3 LOCATE LOG NO S 2 3 Two front log NO S 2 3 are supplied to fit into the space between the metal frame and the ceramic base These logs do not cover the front burner ports but are designed to deflect the front flame back into the fire POSITIONING OF ALL LOGS It is important to follow the log recommended positioning Log NO 6 10 9 and 4 mu...

Page 11: ... charred effect facing toward the right hand side 5 LOCATE LOG NO 6 Place this log on the right hand side of the burner on the rear log in front of the pilot Charred end facing inwards The left hand side of the log is positioned between the metal uprights on the side of the grate LOCATE LOG NO 7 The charred effect of the log is positioned on the smaller coal in the centre of the burner on the righ...

Page 12: ...at the rear of the burner The large log has two holes on the underside to position in place 3 LOCATE LOG NO S 2 3 Two front log no s 2 and 3 are supplied to fit into the space between the metal frame and the ceramic base These logs do not cover the front burner ports but are designed to deflect the front flame back into the fire Only use logs supplied by the manufacturer as other logs may effect c...

Page 13: ...itioned in the same manner but on the right hand side of the burner with the right hand side of the logs positioned between the metal uprights of the grate Two pins are provided to firmly position these two logs onto the large rear log no 1 6 LOCATE LOG NO 7 The charred effect of the log is positioned on the smaller coal in the centre of the burner on the right hand side The right hand side of the...

Page 14: ... to work in a Kemlan Horizon electronic power flue ignition system Working correctly there will be no spillage Unit should cut out if not enough draw to ensure proper functioning 2 Initially the Kemlan coal fire may burn with a slightly blue flame After approximately 20 minutes the fire will settle down and burn with a yellow flame 3 As with all gas fires your gas coal pebble or log fire should be...

Page 15: ...15 Installation Instructions Kemlan Natural Draft Electronic Ignition Gas Fireplaces ...

Page 16: ...ervice information contact Kemlan Australia Head Office 13 French Avenue Brendale Qld 4500 PH 07 3490 5500 FAX 07 3490 5520 www kemlan com Head Office 13 French Avenue Brendale Qld 4500 PH 07 3490 5500 FAX 07 3490 5520 www kemlan com ...

Page 17: ...CHECK ALL CONNECTIONS CHECK SPARK ELECTRODE CONNECTIONS AND REPLACE ELECTRODE IF DAMAGED CHECK SOLENOID CONNECTIONS AT VALVE CHECK PRESSURE SWITCH FUNCTIONS IN FAN Note flash codes red LED for pressure switch functions on module TURN ON ALL POWER SWITCHES CHECK ALL CONNECTIONS CHECK FAN ON INDEPENDENT POWER SWITCH CHECK ELECTRODE IS IN PILOT FLAME CLEAN ELECTRODE CHECK ELECTRODE CONNECTIONS REPLAC...

Page 18: ...ON ALL CONNECTIONS CHECK GAS PRESSURE CHECK PILOT AND CLEAN INJECTOR CHECK ELECTRIC SUPPLY AND TURN ON ALL SWITCHES CHECK ALL CONNECTIONS CHECK SPARK ELECTRODE CONNECTIONS AND REPLACE ELECTRODE IF DAMAGED CHECK SOLENOID CONNECTIONS AT VALVE CHECK ELECTRODE IS IN PILOT FLAME CHECK ELECTRODE CONNETCTIONS CLEAN ELECTRODE CHECK ELECTRODE FOR DAMAGE REPLACE ELECRODE REPLACE MODULE REPLACE VALVE TURN ON...

Page 19: ...n LED will be on 2 1 Maximum retries Check spark electrode for damage exceeded and clean if necessary Check Unit has tried to light electrode connection Check and not detected flame solenoid connections Check gas supply 2 2 Flame fail lockout Check electrode lead Unit has detected loss and connection Check gas supply of flame It has tried re ignition and locked out Fan Forced Models The codes abov...

Page 20: ...t Before carrying out repairs turn off the power visually inspect all cables and connections for damage or corrosion On start up once the unit has passed the self test and pressure switch is closed on fan forced models you should be able to hear a clunk from the gas valve as it opens If no sound from the gas valve check connections If the valve clunks but no ignition check gas supply and spark ele...

Page 21: ...21 Installation Instructions Kemlan Natural Draft Electronic Ignition Gas Fireplaces TAIS Flash Codes LED Flash Code Descriptions ...