14

Installation Instructions Kemlan Natural Draft Electronic Ignition Gas Fireplaces

Commissioning Procedure

Installed correctly the burner should not emit any fumes 

into  the  room.  The  following  procedure  should  be 

undertaken to test that the unit is operating correctly.

1.  After unit has been operating for a short period a 

smoke  match,  smoke  tube,  carbon  dioxide  analyser 

or similar should be directed at the top opening of the 

unit.

2. 

This  procedure  should  be  undertaken  with  the 

following conditions in the room:

•  Open or closed windows

•  Operation of extraction/exhaust fans, range hoods etc

• 

Operation of other gas appliances

• 

Operation of optional appliance fan at any speed.

3.  Should any spillage be detected the cause must be 

rectified before allowing commissioning of unit.

4. 

Please test appliance operation before leaving.

User Instructions

1. 

WARNING  NOTE:  Properly  installed  and  operated 

this  appliance  will  not  leak  gases.  Persistent  fume 

emission must not be tolerated. If fume emission does 

exist, then the following immediate action should be 

taken. 

•  Open doors and windows to ventilate room.

•  Turn the fire off.

•  Check for flue blockage and clear if necessary.

• 

Do not attempt to relight the burner until the cause of 

the emission has been identified and rectified. Should 

assistance be required contact nearest agent.

•  The  gas  burner  is  designed  to  work  in  a  Kemlan 

Horizon electronic power flue ignition system. Working 

correctly there will be no spillage. Unit should cut out if 

not enough draw to ensure proper functioning.

2. 

Initially the Kemlan coal fire may burn with a slightly 

blue flame. After approximately 20 minutes the fire 

will settle down and burn with a yellow flame.

3. 

As with all gas fires your gas coal/pebble or log fire 

should be regularly serviced. We recommend once 

each year. Service information for an authorised 

person to follow has been set out in attached leaflet.

4. 

PLEASE NOTE: Only logs provided by Kemlan 

should be used with this appliance.

5. 

DO NOT place articles on or against this appliance. 

DO NOT use or store flammable materials near this 

appliance.

DO NOT spray aerosols in the vicinity of this appliance 

whilst it is in operation. 

Primarily  a  decorative  appliance  not  certified  as  a 

space heater.

DO NOT MODIFY THIS APPLIANCE

6.  The appliance is a live fuel effect product designed to 

operate with luminous flames and may exhibit slight 

carbon deposition.

7. 

The guard is fitted to this appliance to reduce the risk 

of fire or injury from burns and no part of it should 

be permanently removed. For protection of young 

children or the infirm, a secondary guard is required.

SERVICE  -  WARNING:  ONLY TO  BE  SERVICED 

BY AN AUTHORISED PERSON

Warranty

Provided the appliance has been correctly installed 

according to instructions, Kemlan guarantee the cost of 

replacing parts and the labour in connection therewith for 

a period of 12 months from the date of installation.

Summary of Contents for 1100 Low Line 1000 Mk2 Pebble

Page 1: ...Installation Instructions Horizon Natural Draft Electronic Ignition Gas Fireplaces ...

Page 2: ...k2 Pebble 1400 Mk2 Coal 2000 Low Line 1800 Mk2 Pebble 1800 Mk2 Coal SINGLE SIDED MODELS 700 Low Line 700 Mk2 Pebble 700 Mk2 Coal 700 Ironbark Log Mk4 850 Low Line 800 Mk2 Pebble 800 Mk2 Coal 850 Ironbark Log Mk4 1100 Low Line 1000 Mk2 Pebble 1000 Mk2 Coal 850 Ironbark Log Mk4 1500 Low Line 1400 Mk2 Pebble 1400 Mk2 Coal 2000 Low Line 1800 Mk2 Pebble 1800 Mk2 Coal CANTILEVER 700 Cantilever 700 Mk2 P...

Page 3: ...Natural Draft Electronic Ignition N D E I flue system shall be installed by authorized personnel in accordance with the manufacturer s installation instructions local gas fitting regulations municipal building codes electrical wiring regulations and any other statutory regulations Contact your local building authorities about restrictions and installation inspections that may be required If in dou...

Page 4: ... 435 900 2246 350 300 OPENING DIMENSIONS 770 870 870 1000 1000 SINGLE SIDED 700 Low Line 850 Low Line 700 270 390 365 A B C1 C 850 270 430 405 670 D 770 1000 E 1095 225 F 275 178 G 225 1100 Low Line 1100 270 430 405 770 1358 275 225 1500 Low Line 1500 290 460 435 900 1746 300 250 2000 Low Line 2000 290 460 435 900 2246 300 250 OPENING DIMENSIONS C1 D D HEIGHT OF FIREBOX UNIT USING HEAT ZONE KIT RE...

Page 5: ...onic Ignition Gas Fireplaces Measurements and Specification of N D E I CANTILEVER Cantilever 700 Cantilever 1100 1190 1266 478 440 A A1 B1 B 1424 1500 478 440 455 C 455 225 D 225 275 D1 275 177 E 177 405 F 405 336 G 336 AGA Approved Cowl to suit flue sizes ...

Page 6: ...2293 490 980 510 including 10mm plasterboard SINGLE SIDED 700 Low Line 850 Low Line 1056 410 750 420 A B C B 1145 450 845 460 1100 Low Line 1408 450 845 460 1500 Low Line 1796 480 950 490 2000 Low Line 2296 480 950 490 including 10mm plasterboard 1050 1145 1145 1280 1280 C C INTERNAL FRAME HEIGHT WHEN USING HEAT ZONE KIT REFER TO HEAT ZONE INSTALL PAGE 1050 1145 1145 1280 1280 C C INTERNAL FRAME H...

Page 7: ...7 Installation Instructions Kemlan Natural Draft Electronic Ignition Gas Fireplaces Section SINGLE SIDED SECTION CANTILEVER SECTION SINGLE SIDED ELEVATION CANTILEVER ELEVATION Elevation ...

Page 8: ...ning off wall switch System does not have a high low burner switch Laying the fire Coal Pebble Evenly spread a bag of Vermiculite into the burner tray Tray should be completely filled to the top with Vermiculite to a depth of approximately 45mm Unpack the coals pebbles contained in a clear plastic bag and lay a row of coals pebbles on the vermiculite along the back of the burner tray leaving appro...

Page 9: ...ireplaces Laying the fire Coal Pebble MARK 2 COALS 700 800 600 x 155 MARK 2 PEBBLES 700 800 600 x 155 MARK 2 COALS 1000 992 x 155 MARK 2 PEBBLES 1000 922 x 135 MARK 2 COALS 1400 1400 x 64 MARK 2 PEBBLES 1400 1400 x 64 MARK 2 COALS 1800 1800 x 64 MARK 2 PEBBLES 1800 1800 x 64 ...

Page 10: ...arge log has two holes on the underside to position in place 3 LOCATE LOG NO S 2 3 Two front log NO S 2 3 are supplied to fit into the space between the metal frame and the ceramic base These logs do not cover the front burner ports but are designed to deflect the front flame back into the fire POSITIONING OF ALL LOGS It is important to follow the log recommended positioning Log NO 6 10 9 and 4 mu...

Page 11: ... charred effect facing toward the right hand side 5 LOCATE LOG NO 6 Place this log on the right hand side of the burner on the rear log in front of the pilot Charred end facing inwards The left hand side of the log is positioned between the metal uprights on the side of the grate LOCATE LOG NO 7 The charred effect of the log is positioned on the smaller coal in the centre of the burner on the righ...

Page 12: ...at the rear of the burner The large log has two holes on the underside to position in place 3 LOCATE LOG NO S 2 3 Two front log no s 2 and 3 are supplied to fit into the space between the metal frame and the ceramic base These logs do not cover the front burner ports but are designed to deflect the front flame back into the fire Only use logs supplied by the manufacturer as other logs may effect c...

Page 13: ...itioned in the same manner but on the right hand side of the burner with the right hand side of the logs positioned between the metal uprights of the grate Two pins are provided to firmly position these two logs onto the large rear log no 1 6 LOCATE LOG NO 7 The charred effect of the log is positioned on the smaller coal in the centre of the burner on the right hand side The right hand side of the...

Page 14: ... to work in a Kemlan Horizon electronic power flue ignition system Working correctly there will be no spillage Unit should cut out if not enough draw to ensure proper functioning 2 Initially the Kemlan coal fire may burn with a slightly blue flame After approximately 20 minutes the fire will settle down and burn with a yellow flame 3 As with all gas fires your gas coal pebble or log fire should be...

Page 15: ...15 Installation Instructions Kemlan Natural Draft Electronic Ignition Gas Fireplaces ...

Page 16: ...ervice information contact Kemlan Australia Head Office 13 French Avenue Brendale Qld 4500 PH 07 3490 5500 FAX 07 3490 5520 www kemlan com Head Office 13 French Avenue Brendale Qld 4500 PH 07 3490 5500 FAX 07 3490 5520 www kemlan com ...

Page 17: ...CHECK ALL CONNECTIONS CHECK SPARK ELECTRODE CONNECTIONS AND REPLACE ELECTRODE IF DAMAGED CHECK SOLENOID CONNECTIONS AT VALVE CHECK PRESSURE SWITCH FUNCTIONS IN FAN Note flash codes red LED for pressure switch functions on module TURN ON ALL POWER SWITCHES CHECK ALL CONNECTIONS CHECK FAN ON INDEPENDENT POWER SWITCH CHECK ELECTRODE IS IN PILOT FLAME CLEAN ELECTRODE CHECK ELECTRODE CONNECTIONS REPLAC...

Page 18: ...ON ALL CONNECTIONS CHECK GAS PRESSURE CHECK PILOT AND CLEAN INJECTOR CHECK ELECTRIC SUPPLY AND TURN ON ALL SWITCHES CHECK ALL CONNECTIONS CHECK SPARK ELECTRODE CONNECTIONS AND REPLACE ELECTRODE IF DAMAGED CHECK SOLENOID CONNECTIONS AT VALVE CHECK ELECTRODE IS IN PILOT FLAME CHECK ELECTRODE CONNETCTIONS CLEAN ELECTRODE CHECK ELECTRODE FOR DAMAGE REPLACE ELECRODE REPLACE MODULE REPLACE VALVE TURN ON...

Page 19: ...n LED will be on 2 1 Maximum retries Check spark electrode for damage exceeded and clean if necessary Check Unit has tried to light electrode connection Check and not detected flame solenoid connections Check gas supply 2 2 Flame fail lockout Check electrode lead Unit has detected loss and connection Check gas supply of flame It has tried re ignition and locked out Fan Forced Models The codes abov...

Page 20: ...t Before carrying out repairs turn off the power visually inspect all cables and connections for damage or corrosion On start up once the unit has passed the self test and pressure switch is closed on fan forced models you should be able to hear a clunk from the gas valve as it opens If no sound from the gas valve check connections If the valve clunks but no ignition check gas supply and spark ele...

Page 21: ...21 Installation Instructions Kemlan Natural Draft Electronic Ignition Gas Fireplaces TAIS Flash Codes LED Flash Code Descriptions ...

Reviews: