Input Calibration
PV Input Range
Range Values
Sensor Type
°F
°C
0 %
100 %
S TC
0 to 3100
–18 to 1704
–0.092 mV
17.998 mV
T TC H
-300 to 700
–184 to 371
–5.341 mV
19.097 mV
T TC L
-200 to 500
–129 to 260
–4.149 mV
12.574 mV
W TC H
0 to 4200
–18 to 2315
–0.234 mV
37.075 mV
W TC L
0 to 2240
–18 to 1227
–0.234 mV
22.283 mV
Thermocouple
Differential *
–50 to 150
–46 to 66
–1.54 mV
4.62 mV
Honeywell
Radiamatic
Type RH
Type RI **
0
to
3400
0
to
3400
–18 to 1871
–18 to 1871
0.00 mV
0.00 mV
57.12 mV
60.08 mV
RTD
Alpha = 0.00385 per
IEC-60751 (1995)
100 ohms
100 ohms (low)
200 ohms
500 ohms
–300 to 1200
–300 to 300
–300 to 1200
–300 to 1200
–184 to
649
–184 to
149
–184 to
649
–184 to
649
25.202 ohms
25.202 ohms
50.404 ohms
126.012 ohms
329.289 ohms
156.910 ohms
658.578 ohms
1646.445 ohms
Linear
Milliamps
4 to 20 mA
0 to 20 mA
4.00 mA
0.00 mA
20.00 mA
20.00 mA
Millivolts
0 to 10 mV
0 to 50 mV
0 to 100 mV
0.00 mV
0.00 mV
0.00 mV
10.00 mV
50.00 mV
100.00 mV
Volts
1 to 5 Volts
0 to 5 Volts
0 to 10 Volts
1.00 Volts
0.00 Volts
0.00 Volts
5.00 Volts
5.00 Volts
10.00 Volts
Carbon
Oxygen
0 to 1250 mV
–30 to 510 mV
0.00 mV
–30.00 mV
1250.00 mV
510.00 mV
* The Factory Calibrated
millivolt values for the Thermocouple Differential Input are for a pair
of J thermocouples at an ambient temperature mean of 450
°
F / 232
°
C. Other thermocouple
types and ambient temperature means may be accomplished via Field Calibration of the input,
with the range value limits being –4 mV to +16 mV for the zero and span values.
** The range values for Radiamatic Type RI are customer configurable within the limits shown.