Configuration
Function Prompt
Selections or
Parameter
Lower Display
Range of Setting
Upper Display
Definition
ALM OUT1
LATCHING ALARM OUTPUT 1
—Alarm output 1
can be configured to be Latching or Non-latching.
NoLATCH
LATCH
NoLATCH —Non-latching
LATCH
—Latching
ATTENTION
When configured for latching, the
alarm will stay active after the alarm condition ends
until the RUN/HOLD key is pressed.
BLOCK
ALARM BLOCKING
—Prevents nuisance alarms
when the controller is first powered up. The alarm is
suppressed until the parameter gets to the non-
alarm limit or band. Alarm blocking affects both
alarm setpoints.
DISABLE
ALARM 1
ALARM 2
ALARM12
DISABLE
—Disables blocking
ALARM 1
—Blocks alarm 1 only
ALARM 2
—Blocks alarm 2 only
ALARM12
—Blocks both alarms
ATTENTION
When enabled on power up or initial
enabling via configuration, the alarm will not activate
unless the parameter being monitored has not been
in an alarm condition for a minimum of one control
cycle (167 ms).
DIAGNOST
DIAGNOSTIC
—Monitors the Current Output and/or
Auxiliary Output for an open circuit condition. If either
of these two outputs falls below about 3.5 mA, then
an Alarm is activated. This configuration is in
addition to whatever was selected for AxSxTYPE.
DISABLE
ALARM 1
ALARM 2
DISABLE
—Disables Diagnostic Alarm
ALARM 1
—Alarm 1 is diagnostic alarm
ALARM 2
—Alarm 2 is diagnostic alarm
12/04
UDC3200 Universal Digital Controller Product Manual
91