Configuration
Function Prompt
Selections or
Parameter
Lower Display
Range of Setting
Upper Display
Definition
XMITTER2
B TC
E TC H
E TC L
J TC H
J TC M
J TC L
K TC H
K TC M
K TC L
NNM H
NNM L
NIC H
NIC L
R TC
S TC
T TC H
T TC L
W TC H
W TC L
100 PT
100 LO
200 PT
500 PT
RAD RH
RAD RI
LINEAR
SQROOT
TRANSMITTER CHARACTERIZATION
—This
selection lets you instruct the controller to
characterize a linear input to represent a non-linear
one.
ATTENTION
Prompt only appears when a linear
actuation is selected at prompt IN2 TYPE.
FOR EXAMPLE:
If input 2 is a 4 to 20 mA signal, but the signal
represents a type K thermocouple, then select
K TC
H
and the controller will characterize the 4 to 20 mA
signal so that it is treated as a type K thermocouple
input (high range).
Parameter definitions are the same as in IN2 TYPE.
IN2 HIGH
–999. To 9999. Floating
(in engineering units)
INPUT 2 HIGH RANGE VALUE
in engineering units
is displayed for all inputs but can only be configured
for linear or square root transmitter characterization
See the example in IN1 HI.
IN2 LOW
–999. To 9999. Floating
(in engineering units)
INPUT 2 LOW RANGE VALUE
in engineering units
is displayed for all inputs but can only be configured
for linear or square root transmitter characterization.
See the example in IN1 HI
RATIO 2
–20.00 to 20.00
Floats to 3 decimal places
RATIO ON INPUT 2
—Select the Ratio value you
want on Input 1.
BIAS IN2
–999. to 9999.
(in engineering units)
BIAS ON INPUT 2
— Bias is used to compensate
the input for drift of an input value due to
deterioration of a sensor, or some other cause.
Select the bias value you want on Input 1.
FILTER 2
0 to 120 seconds
No filter = 0
FILTER FOR INPUT 2
—A software digital filter is
provided for Input 1 to smooth the input signal. You
can configure the first order lag time constant from 1
to 120 seconds. If you do not want filtering, enter 0.
BURNOUT
BURNOUT PROTECTION (SENSOR BREAK)
provides most input types with upscale or downscale
protection if the input fails.
NONE
NO BURNOUT
—If Input 2 is being used in the
Control Algorithm (such as the PV or RSP input
parameter), then the pre-configured Failsafe output
(selected in the CONTROL Set up Group) is applied
when a failed input is detected (does not apply for an
input out of range). Diagnostic message IN2 FAIL is
intermittently flashed on the lower display.
12/04
UDC3200 Universal Digital Controller Product Manual
69