Modbus Read, Write and Override Parameters plus Exception Codes
208
UDC2500 Universal Digital Controller Product Manual
4/07
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex
Decimal
Input 2
Transmitter
Characterization
00AB 171
INT
R/W
0 = B TC
1 = E TC H
2 = E TC L
3 = J TC H
4 = J TC M
5 = J TC L
6 = K TC H
7 = K TC M
8 = K TC L
9 = NNM H
10 = NNM L
11 = Nicrosil H TC
12 = Nicrosil L TC
13 = R TC
14 = S TC
15 = T TC H
16 = T TC L
17 = W TC H
18 = W TC L
19 = 100 PT RTD
20 = 100 PT LO RTD
21 = 200 PT RTD
22 = 500 PT RTD
23 = Radiamatic RH
24 = Radiamatic RI
25 = Linear
26 = Square Root
Input 2 High
Range Value
0023
035
FP
R/W
–999. to 9999. Engineering
Units
Input 2 Low
Range Value
0024
036
FP
R/W
–999 to 9999. Engineering
Units
Input 2 Ratio
0025
037
FP
R/W
–20.00 to 20.00
Input 2 Bias
0026
038
FP
R/W
–999 to 9999. Engineering
Units
Input 2 Filter
002B
043
FP
R/W
0 to 120 seconds