Output Calibration
4/07
UDC2500 Universal Digital Controller Product Manual
153
Procedure
The procedure for calibrating the Current Output is listed in Table 6-2. The numeric
codes are also listed. Make sure LOCK in the Tuning Set Up group is set to
NONE.
(See Subsection 3.4 – Tuning Set Up Group.)
Table 6-2 Current Output Calibration Procedure
(Numeric Code 30000)
Step
Operation
Press
Result
1
Enter Calibration
Mode
Setup
Setup
until you see
Upper Display
=
CAL (
- - - -
)
Lower Display
=
CURENT (30000)
2
Calibrate 0 %
Function
Function
Function
You will see:
Upper Display
=
A Value
Lower Display
=
ZROVAL (30001)
or
Until the desired 0 % output is read on the milliammeter,
use the values shown below depending on the action of
your controller. Normally, this will be the setting that
produces 4 mA.
3
Calibrate 100 %
Function
Function
Function
This stores the 0 % value and
you will see:
Upper Display
=
A Value
Lower Display
=
SPNVAL (30002)
or
Until the desired 100 % output is read on the milliammeter,
use the values shown below depending on the action of
your controller. Normally, this will be the setting that
produces 20 mA.
4
Function
Function
Function
The controller stores the span value.
Exit the
Calibration Mode
Lower
Display
Lower
Display
Lower
Display
To exit the calibration mode.