Configuration
40
UDC2500 Universal Digital Controller Product Manual
4/07
Function Prompt
Lower Display
Selection or Range of Setting
Upper Display
English
Numeri
c Code
English
Numeric
Code
Parameter
Definition
FINLSP 203
Enter a value within
the setpoint limits
SETPOINT RAMP FINAL SETPOINT
—
Enter the value desired for the final setpoint.
The controller will operate at the setpoint set
here when ramp is ended.
ATTENTION
If the ramp is on HOLD, the
held setpoint can be changed by the
▲
and
▼
keys. However, the ramp time remaining and
original ramp rate is not changed. Therefore,
when returning to RUN mode, the setpoint
will ramp at the same rate as previous to the
local setpoint change and will stop if the final
setpoint is reached before the time expires. If
the time expires before the final setpoint is
reached, it will jump to the final setpoint.
ATTENTION
SP RAMP and SP RATE will
cause the SP portion of Accutune to abort.
PV Tune will continue to function normally.
Ramp is placed into HOLD while tuning
(TUNE configuration).
SPRATE
SP Rate
operates only
when neither
SP Ramp or
SP
Programming
is running or
when SP
Ramp and SP
Programming
are disabled
204
DIS
ENAB
0
1
SETPOINT RATE
—Lets you configure a
specific rate of change for any local setpoint
change.
DISABLE SETPOINT RATE
—Disables the
setpoint rate option.
ENABLE SETPOINT RATE
—Allows the SP
rate feature.
EUHRUP 205
0 to 9999 in
Engineering units
per hour
RATE UP
—Rate up value. When making a
setpoint change, this is the rate at which the
controller will change from the original
setpoint up to the new one. The ramping
(current) setpoint can be viewed as SPn in
the lower display.
Entering a 0 will imply an immediate change
in Setpoint (i.e., no rate applies).
Summary of Contents for UDC2500
Page 14: ......
Page 241: ...4 07 UDC2500 Universal Digital Controller Product Manual 227 ...
Page 242: ...228 UDC2500 Universal Digital Controller Product Manual 4 07 ...
Page 243: ......