4

 OPERATION 

34 

TWM 9000

www.honeywellprocess.com

34-VF-25-37 iss.2 GLO Jan 18 US

Time Stamp

R

The time when evaluation of the block was started and a 

change in alarm/event state was detected that is unreported. 

The time stamp value will be maintained constant until alert 

confirmation has been received - even if another change of 

state occurs.

Uninitialized

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

Subcode

R

An enumeration specifying the cause of the alert to be 

reported.

Other

Setting:

Other / Block Configuration / Link Configuration / Simulation 

Active / Local Override / Device Fault State / Device 

Maintenance / Input Failure / Output Failure / Memory 

Failure / Lost Static Data / Lost NV Data / Readback Check / 

Maintenance Needed / Power Up / Out Of Service

Value

R

The value of the associated parameter at the time the alert 

was detected.

0

Setting:

0...255

CHANNEL

CHANNEL

CHANNEL

CHANNEL

Channel

Channel

Channel

Channel

R/W

The number of the logical hardware channel that is connected 

to this I/O block. This information defines the transducer to be 

used going to or from the physical world.

Note:

Note:

Note:

Note:

W = Writeable only by setting "OOS" in MODE_BLK

Uninitialized

Setting:
1 (volume flow in m

3

/s)

2 (mass flow in kg/s)

3 (speed in m/s)

4 (coil temperature in 

°

C)

5 (conductivity in S/m)

6 (electronic temperature in 

°

C)

FIELD_VAL

FIELD_VAL

FIELD_VAL

FIELD_VAL

Field Value

Field Value

Field Value

Field Value

R

Raw value of the field device in percent of the PV range, with a 

status reflecting the transducer condition, before signal 

characterization (L_TYPE) or filtering (PV_FTIME).

-

Status

R

Actual Status is displayed.

-

Value

R

Actual Field Value

-

GRANT_DENY

GRANT_DENY

GRANT_DENY

GRANT_DENY

Grant Deny

Grant Deny

Grant Deny

Grant Deny

R/W

Options for controlling access of host computers and local 

control panels to operating, tuning and alarm parameters of 

the block.

-

GRANT

Grant

R/W

Depending on the philosophy of the plant, the operator or a 

higher level device (HLD) or a local operator's panel (LOP) in 

the case of "Local", may turn on an item of the "Grant" 

attribute - "Program, Tune, Alarm or Local".

Uninitialized

Setting:

Program /  Tune /  Alarm /  Local

DENY

Deny

R/W

The deny attribute is provided for use by a monitoring 

application in an interface device and may not be changed by 

an operator.

Uninitialized

Setting:

Program denied / Tune denied / Alarm denied / Local denied

HI_ALM

HI_ALM

HI_ALM

HI_ALM

High Alarm

High Alarm

High Alarm

High Alarm

Mix

The status for High Alarm and its associated time stamp.

Settings of 5 subelements see in the following part.

-

Parameter

Parameter

Parameter

Parameter
Subelement

Access

Description and settings

Initial Value

Summary of Contents for TWM 9000

Page 1: ...n Fieldbus Interface Description of Foundation Fieldbus Interface Electronic Revision ER 3 3 xx SW REV 3 3x TWM 9000 TWM 9000 TWM 9000 TWM 9000 Supplementary Instructions Supplementary Instructions Supplementary Instructions Supplementary Instructions The documentation is only complete when used in combination with the relevant documentation for the flow sensor ...

Page 2: ...on of FOUNDATION Fieldbus 9 3 7 Topology of FF networks 10 4 Operation 11 4 1 Settable functions 11 4 2 Description of the Foundation Fieldbus block system 12 4 3 Used abbreviations 13 4 4 Resource Block RB 14 4 4 1 Foundation Fieldbus parameters for Resource Block 14 4 4 2 Manufacturer specific parameters of the signal converter for Resource Block 20 4 5 Transducer Block TB 25 4 5 1 Foundation Fi...

Page 3: ...ally conductive liquid media Your measuring device is supplied ready for operation The factory settings for the operating data have been made in accordance with your order specifications The following versions are available Compact version the signal converter is mounted directly on the flow sensor Remote version electrical connection to the flow sensor via field current and signal cable INFORMATI...

Page 4: ...1 SAFETY INSTRUCTIONS 4 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...

Page 5: ... x Enhanced Resource Block RB 1 x Customer Transducer Block TB 3 x Analog Input Block AI 2 x Integrator Block IT 1 x Proportional Integral Derivate Block PID Execution time Analog Input Block 10 ms Integrator Block 15 ms Proportional Integral Derivate Block 25 ms Electrical connections Device power supply Not intrinsically safe 9 32 VDC Intrinsically safe 9 24 VDC Basic current 10 5 mA Maximum err...

Page 6: ...2 TECHNICAL DATA 6 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...

Page 7: ...km 4 9 dB mile impedance 100 Ω at 31 25 kHz 3 2 Grounding of flow sensor The flow sensor must be properly connected to ground The grounding cable should not transmit any interference voltages Do not use the grounding cable to connect more than one device to ground In hazardous areas grounding is used at the same time for equipotential bonding The sensors are connected to ground by means of a funct...

Page 8: ...nstallation is strongly recommended Multiple grounding of the shield is of advantage In explosion proof systems the shielding must at least be connected at one end of the cable NAMUR NE 21 compliance is given provided the above recommended cable types are used Core cross section 0 8 mm2 or AWG 18 0 32 mm2 or AWG 22 0 13 mm2 or AWG 26 1 25 mm2 or AWG 16 Cable type A A A A B B B B C C C C D D D D tw...

Page 9: ...The wiring between the device and the FOUNDATION Fieldbus cable is independent of polarity The signal converter FOUNDATION Fieldbus interface will operate only if the additional power supply for the device is connected available For a detailed description of the electrical connections please refer to the standard signal converter handbook or or 1 e g incoming data lines 2 e g outgoing data lines ...

Page 10: ...connect and disconnect the devices without interrupting the bus or the communication 1 HSE network 2 H1 bus 3 Intrinsically safe explosive area B1 B2 Bridge coupling element for H1 bus and HSE network D1 D3 Device field devices own power supply for non potentially explosive areas D4 D6 Intrinsically safe devices external power supply for potentially explosive areas I S Intrinsically safe barrier J...

Page 11: ...ot available for Foundation Fieldbus devices C5 4 2 meas page In case of Foundation Fieldbus device the second measurement page is meant to check the output values of the different function blocks Only Foundation Fieldbus values can be selected here The analogue inputs are shown with exactly the value seen on the bus system C5 4 1 measurement 1 line Select AI1 analog inp AI2 analog inp AI3 analog ...

Page 12: ...ain benefits of Foundation Fieldbus is line saving in comparison to the traditional 4 20 mA technology The different device functions are implemented in a block based scheme within a user application In this block scheme a distinction is made between the Resource Block Transducer Block and Function Block Figure 4 1 Foundation Fieldbus block scheme 1 Resource Block RB 2 Transducer Block TB 3 Functi...

Page 13: ... Block IT Integrator Block PID Proportional Integral Derivate Block RB Resource Block TB Transducer Block R Read W Write R W Read and Write BLK Block mode MAN Manual mode Mix Mix mode R W and R W Auto Automatic mode OOS Out Of Service mode OD Object Directory SP Set Point IV Initial Value PV Process Value factory settings ...

Page 14: ...lock configuration Simulation Active Simulation enabled in this block Local Override Output tracking of faultstate active Device Fault State Device faultstate set Device Maintenance Device needs maintenance soon Input Failure Process variable has bad status Output Failure Failure detected in output hardware Memory Failure Memory error detected Lost Static Data Static parameters cannot be recovered...

Page 15: ...ted states and disabled states of the alarms associated with the function block Uninitialized Current R The active status of each alarm The zero 0 state will be used to indicate alarm clear 0 Unacknowledged R Setting Disc Alm Unack Block Alm Unack Uninitialized Unreported R Setting Disc Alm Unrep Block Alm Unrep Uninitialized Disabled R W Setting Disc Alm Disabled Block Alm Disabled Uninitialized ...

Page 16: ...on methods available for this resource Scheduled Block execution Setting Scheduled Block execution DD_RESOURCE DD_RESOURCE DD_RESOURCE DD_RESOURCE DD Resource DD Resource DD Resource DD Resource R String identifying the tag of the resource which contains the Device Description for this resource 32 blanks DD_REV DD_REV DD_REV DD_REV DD Revision DD Revision DD Revision DD Revision R Revision of the ...

Page 17: ...ITK_VER ITK_VER ITK_VER ITK_VER ITK Version ITK Version ITK Version ITK Version Interoperability Test Kit R Major revision number of the interoperability test case used to register this device 5 Setting 5 LIM_NOTIFY LIM_NOTIFY LIM_NOTIFY LIM_NOTIFY Limit Notify Limit Notify Limit Notify Limit Notify R W Maximum number of unconfirmed notify messages allowed 20 Setting 0 255 MANUFAC_ID MANUFAC_ID MA...

Page 18: ...4294967295 in 1 32 ms TEST_RW TEST_RW TEST_RW TEST_RW Test Read Write Test Read Write Test Read Write Test Read Write R W Read write test parameter used only for conformance testing Note Subelements Value 1 15 have no function UPDATE_EVT UPDATE_EVT UPDATE_EVT UPDATE_EVT Update Event Update Event Update Event Update Event Mix This alert is generated by any change to the static data Unacknowledged R...

Page 19: ...s started and a change in alarm event state was detected that is unreported The time stamp value will be maintained constant until alert confirmation has been received even if another change of state occurs Uninitialized Setting MM DD YY Month Day Year HH MM SS Hour Minute Second Subcode R An enumeration specifying the cause of the alert to be reported Other Setting Other Block Configuration Link ...

Page 20: ...12 24 VDC no option 12 24 VDC capacit Elect 12 24 VDC Virtual Ref 12 24 VDC non Ex Adapter 24 VAC DC no option 24 VAC DC capacit Elect 24 VAC DC Virtual Ref 24 VAC DC non Ex Adapter DISPLAY_OPTION Display Option R Setting Configuration error or missing Standard Eastern Europe Northern Europe Southern Europe Far East Japanese Chinese Russian as ordered IO_SELECTION IO1 Modules IO R Setting configur...

Page 21: ... GDC Communication Startup GDC data invalid Startup Sensor data valid C Number doesn t match to FF Software Hardware changed C raw C detected Data Base doesn t match to FF Software MODE_BLK PERMITTED doesn t include Auto MODE_BLK TARGET is set OOS GDC bold F message GDC F message write from GDC to RB TB doesn t work GDC Mfr unknown GDC serial number Boardinfo incomplete or corrupt action write fro...

Page 22: ...G Current diagnosis PID_DIAG PID Diagnosis R Setting Startup Device RB MODE_BLK ACTUAL is OOS Memory failure no schedule period of execution period of execution to large MODE_BLK PERMITTED doesn t include Auto MODE_BLK TARGET is set OOS MODE_BLK TARGET is set MAN MODE_BLK ACTUAL is MAN Startup to Auto BYPASS is uninitialized SHED_OPT is uninitialized PV_SCALE EU_100 EU_0 OUT_SCALE EU_100 EU_0 TRK_...

Page 23: ... overflow counter 1 FB2 overflow counter 2 FB3 backplane invalid overflow counter 1 overflow counter 3 FB4 checks in progress C C C C test sensor simulation fieldbus I I I I counter 1 stopped FB2 counter 2 stopped FB3 power fail counter 1 stopped counter 3 stopped FB4 power fail control input A active control input B active over range display 1 over range display 2 backplane sensor backplane setti...

Page 24: ...tion Hour Operation Hour R Operation hour since first start up Actual values PASSWRD PASSWRD PASSWRD PASSWRD Password Password Password Password R W Password to activate access rights to restricted parameters 0 PROTECT_INFO PROTECT_INFO PROTECT_INFO PROTECT_INFO Protection Information Protection Information Protection Information Protection Information R Current protection level to restricted para...

Page 25: ...ive Simulation enabled in this block Local Override Output tracking of faultstate active Device Fault State Device faultstate set Device Maintenance Device needs maintenance soon Input Failure Process variable has bad status Output Failure Failure detected in output hardware Memory Failure Memory error detected Lost Static Data Static parameters cannot be recovered Lost NV Data Non volatile parame...

Page 26: ... task another block alert may be reported without clearing the Active status if the subcode has changed Unacknowledged R W A discrete enumeration which is set to Unacknowledged when an alarm occurs and set to Acknowledged by a write from a human interface device or other entity which can acknowledge that the alarm event has been noticed Uninitialized Setting Uninitialized Acknowledged Unacknowledg...

Page 27: ... refer sheet Device Error Mapping The time when evaluation of the block was started and a change in alarm event state was detected that is unreported The time stamp value will be maintained constant until alert confirmation has been received even if another change of state occurs Time stamp records the time when parameter was updated Uninitialized Setting MM DD YY Month Day Year HH MM SS Hour Minu...

Page 28: ...lue R W GKL Fct C1 1 5 10 5 Setting 0 5 20 0 GKH_Value R W GKH Fct C1 1 6 5 0 Setting 0 5 12 0 Coil_Resist_Rsp R W Coil resistance Rsp Fct C1 1 7 60 0 Setting 10 0 220 0 Coil_Temp_Calc R W Calibration coil temperature Fct C1 1 8 293 15 Setting 233 15 473 15 Density_Fact R W Density Fct C1 1 9 1000 0 Setting 100 0 5000 0 EF_Electr_Fact R W Calibrate electrode factor EF Fct C1 1 11 manual setting 0 ...

Page 29: ... 0 0 10 00 PRIMARY_VALUE PRIMARY_VALUE PRIMARY_VALUE PRIMARY_VALUE PRIMARY_VALUE_ PRIMARY_VALUE_ PRIMARY_VALUE_ PRIMARY_VALUE_ RANGE RANGE RANGE RANGE R W There are 6 Primary Values 1 6 Setting is for all identical Therefore the description follows only for Primary Value 1 Setting 1 volume flow in m3 s 2 mass flow in kg s 3 speed in m s 4 coil temperature in C 5 conductivity in S m 6 electronic te...

Page 30: ...t of the decimal point which should be used by an interface device in displaying the specified parameter 0 Setting 0 255 SELF_TEST_C1_3 SELF_TEST_C1_3 SELF_TEST_C1_3 SELF_TEST_C1_3 R W Self test Fct C1 3 Empty_Pipe R W empty pipe detect Fct C1 3 1 0 Setting 0 off 1 conductivity 2 cond empty pipe S 3 cond empty pipe F Limit_Empty_Pipe R W limit empty pipe Fct C1 3 2 0 006 Setting 0 0 0 9999 Full_Pi...

Page 31: ...s included in all the 4 views as per definition given in the standard pressure transducer block given by FF Other XD_ERROR XD_ERROR XD_ERROR XD_ERROR Transducer Error Transducer Error Transducer Error Transducer Error R One of the transducer error codes defined in the FF Transducer Specifications in Block Alarm Subcodes 0 Setting 16 Unspecified error An error has occurred that was not identified 1...

Page 32: ...enabled in this block Local Override Output tracking of faultstate active Device Fault State Device faultstate set Device Maintenance Device needs maintenance soon Input Failure Process variable has bad status Output Failure Failure detected in output hardware Memory Failure Memory error detected Lost Static Data Static parameters cannot be recovered Lost NV Data Non volatile parameters cannot be ...

Page 33: ...lert status unacknowledged states unreported states and disabled states of the alarms associated with the function block Current R Setting HiHi Alarm Hi Alarm LoLo Alarm Lo Alarm Block Alarm Uninitialized Unacknowledged R Setting HiHi Alarm Unack Hi Alarm Unack LoLo Alarm Unack Lo Alarm Unack Block Alarm Unack Uninitialized Unreported R Setting HiHi Alarm Unrep Hi Alarm Unrep LoLo Alarm Unrep Lo A...

Page 34: ...n kg s 3 speed in m s 4 coil temperature in C 5 conductivity in S m 6 electronic temperature in C FIELD_VAL FIELD_VAL FIELD_VAL FIELD_VAL Field Value Field Value Field Value Field Value R Raw value of the field device in percent of the PV range with a status reflecting the transducer condition before signal characterization L_TYPE or filtering PV_FTIME Status R Actual Status is displayed Value R A...

Page 35: ...I_PRI HI_PRI HI_PRI High Priority High Priority High Priority High Priority R W Priority of the High Alarm Setting see in the following part 1 Setting range for previous 2 parameters x_y_LIM x_y_Limit 3 39 E38 3 39 E38 INF infinite INF infinite Setting for previous 2 parameters x_y_PRI x_y_Priority 0 The associated alert may clear when the priority is changed to 0 but it will never occur 1 The ass...

Page 36: ...Priority Low Priority Low Priority Low Priority R W Priority of the Low Alarm Setting see in the following part 1 LO_LO_PRI LO_LO_PRI LO_LO_PRI LO_LO_PRI Low Low Priority Low Low Priority Low Low Priority Low Low Priority R W Priority of the Low Low Alarm Setting see in the following part 1 Setting range for previous 2 parameters x_y_LIM x_y_Limit 3 39 E38 3 39 E38 INF infinite INF infinite Settin...

Page 37: ...0 Setting 0 0 60 0 SIMULATE SIMULATE SIMULATE SIMULATE Simulate Simulate Simulate Simulate Mix Allows the transducer analogue input or output to the block to be manually supplied when Simulate is enabled When simulation is disabled the simulate value and status track the actual value and status Simulate Status R W Used for the transducer status when simulation is enabled Bad Non Specific Non Limit...

Page 38: ...right of the decimal point used with the value obtained from the transducer for a specified channel Note Note Note Note W Writeable only by setting OOS in MODE_BLK EU_100 Engineering Unit 100 R W The engineering unit value which represents the upper end of range of the associated block parameter 100 EU_0 Engineering Unit 0 R W The engineering unit value which represents the lower end of range of t...

Page 39: ...specific error active Block Configuration Error detected in block configuration Simulation Active Simulation enabled in this block Local Override Output tracking of faultstate active Device Fault State Device faultstate set Device Maintenance Device needs maintenance soon Input Failure Process variable has bad status Output Failure Failure detected in output hardware Memory Failure Memory error de...

Page 40: ...the alert reporting task another block alert may be reported without clearing the Active status if the subcode has changed UNACKNOWLEDGED Unacknowledged R W A discrete enumeration which is set to Unacknowledged when an alarm occurs and set to Acknowledged by a write from a human interface device or other entity which can acknowledge that the alarm event has been noticed Uninitialized Setting Unini...

Page 41: ...ocal may turn on an item of the Grant attribute Program Tune Alarm or Local Uninitialized Setting Program Tune Alarm Local DENY Deny R W The denied attribute is provided for use by a monitoring application in an interface device and may not be changed by an operator Uninitialized Setting Program denied Tune denied Alarm denied Local denied IN_1 IN_1 IN_1 IN_1 Input 1 Input 1 Input 1 Input 1 R W In...

Page 42: ...set must be preceded by a reset confirmation by the control system Generate reset event in case of reset automatic or manual an event notification will be sent to the control system This function is an option and not supported N_RESET N_RESET N_RESET N_RESET Number of Reset Number of Reset Number of Reset Number of Reset R Counts the number of resets It can not be written nor reset OP_CMD_INT OP_C...

Page 43: ...SE_VAL1 PULSE_VAL1 PULSE_VAL1 Pulse Value 1 Pulse Value 1 Pulse Value 1 Pulse Value 1 R W Determines the mass volume or energy per pulse 0 0 Setting Positive or 0 PULSE_VAL2 PULSE_VAL2 PULSE_VAL2 PULSE_VAL2 Pulse Value 2 Pulse Value 2 Pulse Value 2 Pulse Value 2 R W Determines the mass volume or energy per pulse 0 0 Setting Positive or 0 RESET_CONFIRM RESET_CONFIRM RESET_CONFIRM RESET_CONFIRM Rese...

Page 44: ...me Unit 1 Time Unit 1 R W Converts the rate time units in seconds Uninitialized Setting 1 seconds 2 minutes 3 hour 4 days TIME_UNIT2 TIME_UNIT2 TIME_UNIT2 TIME_UNIT2 Time Unit 2 Time Unit 2 Time Unit 2 Time Unit 2 R W Converts the rate time units in seconds Uninitialized Setting 1 seconds 2 minutes 3 hour 4 days TOTAL_SP TOTAL_SP TOTAL_SP TOTAL_SP Total Setpoint Total Setpoint Total Setpoint Total...

Page 45: ...D YY Month Day Year HH MM SS Hour Minute Second STATIC_REVISION Static Revision R The static revision of the block whose static parameter was changed and is being reported It is possible for the present value of static revision to be greater than this because static can be changed at any time 0 RELATIVE_INDEX Relative Index R The OD index of the static parameter whose change caused this alert minu...

Page 46: ...ice Maintenance Device needs maintenance soon Input Failure Process variable has bad status Output Failure Failure detected in output hardware Memory Failure Memory error detected Lost Static Data Static parameters cannot be recovered Lost NV Data Non volatile parameters cannot be recovered Readback Check Failure detected in READBACK Maintenance Needed Device NEEDS maintenance NOW Power Up Recover...

Page 47: ...resis Alarm Hysteresis Alarm Hysteresis R W Amount the PV must return within the alarm limits before the alarm condition clears Alarm hysteresis expressed as a percent of the span of the PV 0 5 Setting 0 0 50 0 ALARM_SUM ALARM_SUM ALARM_SUM ALARM_SUM Alarm Summary Alarm Summary Alarm Summary Alarm Summary Mix The current alert status unacknowledged states unreported states and disabled states of t...

Page 48: ...W The block alarm is used for all configuration hardware connection failure or system problems in the block The cause of the alert is entered in the subcode field The first alert to become active will set the Active status in the Status attribute As soon as the Unreported status is cleared by the alert reporting task another block alert may be reported without clearing the Active status if the sub...

Page 49: ...er failure OutOfService Block actual mode is Out of Service VALUE Value R The value of the associated parameter at the time the alert was detected 0 Setting 0 255 BYPASS BYPASS BYPASS BYPASS Bypass Bypass Bypass Bypass R W The normal control algorithm may be bypassed through this parameter When bypass is set the setpoint value in percent will be directly transferred to the output To prevent a bump...

Page 50: ...SP or the PV normally BKCAL_OUT is the working SP Restrict SP to limits in Cas and RCas If this option is selected the setpoint will be restricted to the setpoint absolute and rate limits in Cas and Rcas modes No output limits in Man Do not apply OUT_HI_LIM or OUT_LO_LIM when target and actual modes are Man DV_HI_ALM DV_HI_ALM DV_HI_ALM DV_HI_ALM Deviation High Alarm Deviation High Alarm Deviation...

Page 51: ...hether it has been reported Uninitialized Setting Uninitialized Clear reported Alarm not active and reported Clear not reported Alarm not active and not reported Active reported Alarm active and reported Active not reported Alarm active and not reported TIME_STAMP Time Stamp R The time when evaluation of the block was started and a change in alarm event state was detected that is unreported The ti...

Page 52: ...larm parameters of the block GRANT Grant R W Depending on the philosophy of the plant the operator or a higher level device HLD or a local operator s panel LOP in the case of Local may turn on an item of the Grant attribute Program Tuning Alarm or Local No option selected Setting Program Host may change mode setpoint or output of block Tune Host may change the tuning parameters of block Alarm Host...

Page 53: ...ociated time stamp UNACKNOWLEDGED Unacknowledged R W A discrete enumeration which is set to Unacknowledged when an alarm occurs and set to Acknowledged by a write from a human interface device or other entity which can acknowledge that the alarm event has been noticed Uninitialized Setting Uninitialized Acknowledged Unacknowledged ALARM_STATE Alarm State R A discrete enumeration which gives an ind...

Page 54: ...event has been noticed Uninitialized Setting Uninitialized Acknowledged Unacknowledged ALARM_STATE Alarm State R A discrete enumeration which gives an indication of whether the alert is active and whether it has been reported Uninitialized Setting Uninitialized Clear reported Alarm not active and reported Clear not reported Alarm not active and not reported Active reported Alarm active and reporte...

Page 55: ... alert was detected 0 LO_LO_LIM LO_LO_LIM LO_LO_LIM LO_LO_LIM Low Low Limit Low Low Limit Low Low Limit Low Low Limit R W The setting for Low Low Alarm in engineering units INF LO_LO_PRI LO_LO_PRI LO_LO_PRI LO_LO_PRI Low Low Priority Low Low Priority Low Low Priority Low Low Priority R W Priority of the Low Low Alarm 0 Setting 0 15 LO_PRI LO_PRI LO_PRI LO_PRI Low Priority Low Priority Low Priority...

Page 56: ... range of the associated block parameter 100 EU_0 EU at 0 R W The engineering unit value which represents the lower end of range of the associated block parameter 0 UNITS_INDEX Units Index R W Device Description units code index for the engineering unit descriptor for the associated block value Uninitialized Setting All units are possible DECIMAL Decimal R W The number of digits to the right of th...

Page 57: ...s to target remote mode after communications are re established NormalShed_NoReturn Target mode changes to next lowest priority non remote mode permitted ShedToRetainedTarget_NormalReturn Shed to previous target mode and return target remote mode after communications are re established ShedToRetainedTarget_NoReturn Target mode changes to target retained mode SP SP SP SP Setpoint Setpoint Setpoint ...

Page 58: ...SCALE TRK_SCALE TRK_SCALE TRK_SCALE Tracking Scale Tracking Scale Tracking Scale Tracking Scale R W The high and low scale values engineering units code and number of digits to the right of the decimal point associated with TRK_VAL EU_100 EU at 100 R W The engineering unit value which represents the upper end of range of the associated block parameter 100 EU_0 EU at 0 R W The engineering unit valu...

Page 59: ...if another change of state occurs Uninitialized Setting MM DD YY Month Day Year HH MM SS Hour Minute Second STATIC_REVISION Static Revision R The static revision of the block whose static parameter was changed and is being reported It is possible for the present value of static revision to be greater than this because static can be changed at any time 0 RELATIVE_INDEX Relative Index R The OD index...

Page 60: ...4 OPERATION 60 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...

Page 61: ...OPERATION 4 61 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...

Page 62: ...4 OPERATION 62 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...

Page 63: ...OPERATION 4 63 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...

Page 64: ...Sam Houston Pkwy S Houston TX 77042 Houston TX 77042 Houston TX 77042 Houston TX 77042 www honeywellprocess com www honeywellprocess com www honeywellprocess com www honeywellprocess com Honeywell International Inc Honeywell International Inc Honeywell International Inc Honeywell International Inc Subject to change without notice Subject to change without notice Subject to change without notice Su...

Reviews: