4.5.2 Manufacturer specific parameters of the signal converter for Transducer Block
Parameter
Parameter
Parameter
Parameter
Subelement
Access
Description and settings
Initial Value
CALIBRATION_C1_1
CALIBRATION_C1_1
CALIBRATION_C1_1
CALIBRATION_C1_1
Write Alarm
Write Alarm
Write Alarm
Write Alarm
Mix
Calibration (Fct. C1.1)
-
Zero_Point
R/W
Zero calibration (manual setting) (Fct. C1.1.1)
0.0
Setting:
-1.0
…
1.0
Size_Entry
R
Size entry (Fct. D2.4)
2
Setting:
1: value in [m] / 2: table [mm & inch]
Sensor_Size_Tab
R/W
Size (Fct. C1.1.2)
2000
Setting:
DN2.5
…
3000 [mm] 1/10"
…
120"
Sensor_Size_Val
R/W
Size (Fct. C1.1.2)
0.2
Setting:
0.0025
…
3.000 [m]
GK_Selection GK
R/W
GK selection (Fct. C1.1.3)
0
Setting:
0: GK & GKL / 1: GK / 2: GKL 3: GKH
GK_Value
R/W
GK (Fct. C1.1.4)
5.0
Setting:
0.5
…
12.0
GKL_Value
R/W
GKL (Fct. C1.1.5)
10.5
Setting:
0.5
…
20.0
GKH_Value
R/W
GKH (Fct. C1.1.6)
5.0
Setting:
0.5
…
12.0
Coil_Resist_Rsp
R/W
Coil resistance Rsp (Fct. C1.1.7)
60.0
Setting:
10.0
…
-220.0
Coil_Temp_Calc
R/W
Calibration coil temperature (Fct. C1.1.8)
293.15
Setting:
233.15
…
473.15
Density_Fact
R/W
Density (Fct. C1.1.9)
1000.0
Setting:
100.0
…
5000.0
EF_Electr_Fact
R/W
Calibrate electrode factor EF (Fct. C1.1.11) (manual setting)
0.003
Num_Electrodes
R/W
Number of electrodes (Fct. C1.1.12)
0
Field_Frequency
R/W
Field frequency (Fct. C1.1.13)
7
COLLECTION_
COLLECTION_
COLLECTION_
COLLECTION_
DIRECTORY
DIRECTORY
DIRECTORY
DIRECTORY
Collection Directory
Collection Directory
Collection Directory
Collection Directory
R
A directory that specifies the number, starting indices and DD
Item IDs of the data collections in each transducer within a
Transducer Block.
-
FILTER_C1_2
FILTER_C1_2
FILTER_C1_2
FILTER_C1_2
Write Alarm
Write Alarm
Write Alarm
Write Alarm
R/W
Filter (Fct. C1.2)
-
Limitation_Low
R/W
Limitation min process input (Fct. C1.2.1)
-12.0
Setting:
-100.000
…
-0.001
Summary of Contents for TWM 9000
Page 4: ...1 SAFETY INSTRUCTIONS 4 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...
Page 6: ...2 TECHNICAL DATA 6 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...
Page 60: ...4 OPERATION 60 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...
Page 61: ...OPERATION 4 61 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...
Page 62: ...4 OPERATION 62 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...
Page 63: ...OPERATION 4 63 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...