OPERATION
4
57
TWM 9000
www.honeywellprocess.com
34-VF-25-37 iss.2 GLO Jan 18 US
STATUS
Status
R
Status of ROUT_IN
-
VALUE
Value
R
Value of ROUT_IN
-
ROUT_OUT
ROUT_OUT
ROUT_OUT
ROUT_OUT
Remote Out Output
Remote Out Output
Remote Out Output
Remote Out Output
R
Block output and status - provided to a host for back
calculation in ROut mode and to allow action to be taken under
limited conditions or mode change.
-
STATUS
Status
R
Status of ROUT_OUT
-
VALUE
Value
R
Value of ROUT_OUT
-
SHED_OPT
SHED_OPT
SHED_OPT
SHED_OPT
Shed Options
Shed Options
Shed Options
Shed Options
R/W
Defines action to be taken on remote control device timeout.
Uninitialized
Setting:
•
Uninitialized
•
NormalShed_NormalReturn: Actual mode changes to next
lowest priority non-remote mode permitted, but returns to
target remote mode after communications are re-
established
•
NormalShed_NoReturn: Target mode changes to next
lowest priority non-remote mode permitted
•
ShedToAuto_NormalReturn: Actual mode changes to "Auto",
but returns to target remote mode after communications are
re-established
•
ShedToAuto_NoReturn: Target mode changes to "Auto"
•
ShedToManual_NormalReturn: Actual mode changes to
"Manual", but returns to target remote mode after
communications are re-established
•
NormalShed_NoReturn: Target mode changes to next
lowest priority non-remote mode permitted
•
ShedToRetainedTarget_NormalReturn: Shed to previous
target mode and return target remote mode after
communications are re-established
•
ShedToRetainedTarget_NoReturn: Target mode changes to
target retained mode
SP
SP
SP
SP
Setpoint
Setpoint
Setpoint
Setpoint
R/W
Setpoint
0
STATUS
Status
Status of SP
VALUE
Value
Value of SP
SP_HI_LIM
SP_HI_LIM
SP_HI_LIM
SP_HI_LIM
Setpoint High Limit
Setpoint High Limit
Setpoint High Limit
Setpoint High Limit
R/W
The setpoint high limit is the highest setpoint operator entry
that can be used for the block.
100
SP_LO_LIM
SP_LO_LIM
SP_LO_LIM
SP_LO_LIM
Setpoint Low Limit
Setpoint Low Limit
Setpoint Low Limit
Setpoint Low Limit
R/W
The setpoint low limit is the highest setpoint operator entry
that can be used for the block.
0
SP_RATE_DN
SP_RATE_DN
SP_RATE_DN
SP_RATE_DN
Setpoint Rate Down
Setpoint Rate Down
Setpoint Rate Down
Setpoint Rate Down
R/W
Ramp rate at which downward setpoint changes are acted on
in "Auto" mode, in PV units per second. If the ramp rate is set
to zero or the block is in a mode other than "Auto", then the
setpoint will be used immediately.
+INF
Setting:
0.0...+INF
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value
Summary of Contents for TWM 9000
Page 4: ...1 SAFETY INSTRUCTIONS 4 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...
Page 6: ...2 TECHNICAL DATA 6 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...
Page 60: ...4 OPERATION 60 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...
Page 61: ...OPERATION 4 61 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...
Page 62: ...4 OPERATION 62 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...
Page 63: ...OPERATION 4 63 TWM 9000 www honeywellprocess com 34 VF 25 37 iss 2 GLO Jan 18 US ...