TH8320ZW1000
9
69-2486—03
Setup functions
Settings & Options
(factory default in
bold
)
0530
Adaptive Intelli-
gent Recovery™
1
On
0 Off
0540
Program periods
4
4 program periods (Wake, Leave, Return, Sleep)
2
2 program periods (Wake, Sleep)
0580
Compressor
protection
5
5 minute compressor off time
[Other options: 0, 1, 2, 3 or 4-minute off time]
0600
Heat temperature
range stop
90 Max. heat temperature setting is 90°F (32°C)
[Other options: 40-89°F (4°C to 32°C)]
0610
Cool temperature
range stop
50 Min. cool temperature setting is 50°F (10°C)
[Other options: 51-99°F (11°C to 37°C)]
0615
Energy Saving
Heat Setpoint
65 65°F (18.5°C)
40-90°F (4.5°C to 32°C)
0616
Energy Saving
Cooling Setpoint
78 78°F (25.5°C)
50-99°F (10°C to 37°C)
0640
Clock format
12 12-hour time (i.e., “3:30 pm”)
24 24-hour time (i.e., “15:30”)
0650
Extended fan
timer (heat)
0 Off
90 Fan runs for 90 seconds after call for heat ends
[Other options: 30, 60, 120]
0660
Extended fan
timer (cool)
0 Off
90 Fan runs for 90 seconds after call for cooling ends
[Other options: 30, 60, 120]
0670
Keypad lock
0
Keypad unlocked (fully functional)
1
Partially locked (access to temperature settings only)
2
Fully locked
0680
Heat temperature
control
2
Standard temperature control (recommended)
1
Choose if room is warmer than set temperature
3
Choose if room does not reach set temperature
0690
Cool temperature
control
2
Standard temperature control (recommended)
1
Choose if room is cooler than set temperature
3
Choose if room does not reach set temperature
0700
Temperature
display offset
0
Thermostat displays actual room temperature
[Other options: -3, -2, -1, 1, 2, 3°F offset (-1.5°C to 1.5°C)]
0710
Reset
0
No reset
1
Reset installer options (including Z-Wave inclusion) & program
schedule to factory default (only date and time settings are
retained)
rf10
Z-Wave Network
Connection
0 Remove
1 Add
rf20
Z-Wave Node
Connection
0 Idle
1
Send Node
Installer setup