INSTALLATION
Page 17
Harsh environment
In the harsh environment where the electromagnetic noise is very
High the connections have to be:
-
LON cable = unshielded or shielded with the shield connected to
Earth in an only point and separate to the internal Ground
-
Power input cable = shielded with the shield connected to Earth
in an only point and separate to the internal Ground
-
Inputs cable = shielded as in the Figure 3
-
Output = use direct outs only if the load is at a distance less
than 3 mt with an unshielded cable well separate to others
cables.
If the load distance is more than 3 mt use the external relays to
mount close to the RTUA01P at a distance less than 3 mt,
connected with an unshielded cable well separate to others cables.