INSTALLATION
Page 9
Connecting to load
Connect each of the cables from the load to one of the 4 available
output connectors, as shown in Figure 7. Internally, all of the output
lines are provided with Power Mosfet that can drive to ground:
1,2A 30V continuous
5A 30V (0,5 sec) peak current for inductive loads
When the cables go outdoor is mandatory to use shielded cables. The
cables’ shielding must be connected to the respective ground
connectors (-V).
For internal wiring without shielded cables is recommended an
electrical environment where the cables are well separated, even at
short runs, especially to the power cables or external cables which
can be essentially subjected to interference or lighting.