Revision 3
STT850
Temperature Transmitter User’s Manual
Page 71
Notes
1.
Operating Parameters:
4-20 mA/DE/HART (Loop Terminal)
Terminals 1, 2: Voltage= 11 to 42 V Current= 4-20 mA Normal (3.8 – 23 mA Faults)
OPTIONAL DIGITAL OUTPUT:
Terminals 4 and 9: Voltage 4 to 30 V Current 40 ma max
FF (Loop Terminal)
Voltage= 9 to 32 V
Current= 25 mA
2. Intrinsically Safe Entity Parameters
For details see Control Drawing on page 67.
Summary of Contents for STT850 SMARTLINE
Page 75: ...Revision 3 STT850 Temperature Transmitter User s Manual Page 65 ...
Page 76: ...Page 66 STT850 Temperature Transmitter User s Manual Revision 3 ...
Page 77: ...Revision 3 STT850 Temperature Transmitter User s Manual Page 67 ...
Page 84: ...Page 74 STT850 Temperature Transmitter User s Manual Revision 3 A 6 Control Drawing ...
Page 85: ...Revision 3 STT850 Temperature Transmitter User s Manual Page 75 ...
Page 86: ...Page 76 STT850 Temperature Transmitter User s Manual Revision 3 ...
Page 87: ...Revision 3 STT850 Temperature Transmitter User s Manual Page 77 ...
Page 88: ...Page 78 STT850 Temperature Transmitter User s Manual Revision 3 ...
Page 89: ...Revision 3 STT850 Temperature Transmitter User s Manual Page 79 ...