Revision 3
STT850
Temperature Transmitter User’s Manual
Page 31
Table 10
–
Transmitter Setup Menus
<Return> Return to the Level 1 menu
Device
Setup
<Return>
Tag ID
(HART/DE only)
Enter Tag ID name up to 8
characters long.
= any
Alphanumeric value
Press
to
enter menu
selection
and
to
select
Alphanumeric
to enter
and shift to
next
character to
the right.
Damping (sec)
(HART/DE only)
##. #
Selection applies digital filtering to
suppress noise effects on the PV.
The limits for this value are 0.0 to
32.0 seconds
NAMUR Output
(HART/DE only)
Disabled
Disabling sets the loop output and
burnout levels to the Honeywell
levels
Enabled
Enabling sets the loop output and
burnout levels to the NAMUR
levels
Loop Ctrl Mode
(Dual Inputs only)
(HART/DE only)
(Read only for DE)
Average,
Differential,
Sensor 1,
Sensor 2,
Split-Range,
Redundant
Mode of Loop control
Loop Ctrl Src
(HART only)
Sensor 1,
Sensor 2
Input sensor currently controlling
the Loop
Delta Limit
(Dual Inputs only)
(HART/FF only)
####.##
User can configure the Delta
Limit. If the Critical Excess Delta
Detection has also been enabled,
the critical fault will be set when
the PV Delta (Sensor 1-Sensor 2
value) exceeds the Delta Limit."
Bumpless Damping
(HART/FF only)
##.#
Damping value for the transition
of Loop Control between Sensors
when Loop Ctrl Mode is Split-
Range or Redundant
Hysteresis
(Dual Inputs only)
(HART/FF only)
###.##
Hysteresis value relative to the
MRV for the transition of Loop
Control between Sensors when
Loop Ctrl Mode is Split-Range
Break Detect*
Enable,
Disable
When enabled, adds a constant
bias value to the Sensor 2
measured value to equate it to the
Sensor 1 measured value at the
moment selected.
* Spurious readings may occur if Break Detect is off in delta mode
Summary of Contents for STT850 SMARTLINE
Page 75: ...Revision 3 STT850 Temperature Transmitter User s Manual Page 65 ...
Page 76: ...Page 66 STT850 Temperature Transmitter User s Manual Revision 3 ...
Page 77: ...Revision 3 STT850 Temperature Transmitter User s Manual Page 67 ...
Page 84: ...Page 74 STT850 Temperature Transmitter User s Manual Revision 3 A 6 Control Drawing ...
Page 85: ...Revision 3 STT850 Temperature Transmitter User s Manual Page 75 ...
Page 86: ...Page 76 STT850 Temperature Transmitter User s Manual Revision 3 ...
Page 87: ...Revision 3 STT850 Temperature Transmitter User s Manual Page 77 ...
Page 88: ...Page 78 STT850 Temperature Transmitter User s Manual Revision 3 ...
Page 89: ...Revision 3 STT850 Temperature Transmitter User s Manual Page 79 ...