OPERATOR MANUAL // SECTION 3: MAINTENANCE AND
TROUBLESHOOTING
HONEYWELL
18
TABLE 2: Configuration Dip Switch Settings
Verification Time
DIP SWITCH
1
DIP SWITCH
2
DIP SWITCH
3
DESCRIPTION
closed
closed
closed
Verify is disabled & the Verify Relay is unused.
Factory setting
.
closed
open
open
Verify is enabled and the Verify time is 5 seconds.
open
closed
open
Verify is enabled and the Verify time is 10 seconds.
closed
closed
open
Verify is enabled and the Verify time is 15 seconds.
open
open
closed
Verify is enabled and the Verify time is 20 seconds.
closed
open
closed
Verify is enabled and the Verify time is 25 seconds.
open
closed
closed
Verify is enabled and the Verify time is 30 seconds.
open
open
open
Verify is disabled and the Verify Relay operates as a
second Fire Relay.
Latching
DIP SWITCH
4
DESCRIPTION
open
Non-Latching mode. If Verify is enabled then the Verify Relay will de-energize
approximately 10 seconds after it energizes. If Verify is disabled then the Fire
Relay(s) will de-energize approximately 10 seconds after it energizes.
closed
Latching mode. If Verify is enabled then when the Verify Relay energizes it will
remain energized until the detector is reset. If Verify is disabled then when the
Fire Relay energizes it will remain energized until the detector is reset.
Factory setting.
Test Cycle
DIP SWITCH
6
DESCRIPTION
open
Testing of the Lens occurs every 30 minutes
. Factory setting.
closed
Testing of the Lens occurs every 6 minutes
Fire Range
DIP SWITCH
7
DIP SWITCH
8
DESCRIPTION
open
open
The detector is set to detect an industry standard 1 sq. ft. fire at
15 feet on axis.
closed
open
The detector is set to detect an industry standard 1 sq. ft. fire at
30 feet on axis.
open
closed
The detector is set to detect an industry standard 1 sq. ft. fire at
45 feet on axis.