DETECTOR PINOUT DATA
TABLE 1: Stand-Alone Model SS4-AI Detector Connectors - Pinouts
J1:
DETECTOR INPUT POWER
PIN
1
DC Return or Ground (-)
2
NOT USED (Do not connect to this Pin.)
3
NOT USED (Do not connect to this Pin.)
4
Power (+24 Volts DC)
J2:
DETECTOR POWER OUT
PIN
1
DC Return or Ground (-)
2
NOT USED (Do not connect this Pin.)
3
NOT USED (Do not connect this Pin.)
4
Power (+24 Volts DC)
J4:
FIRE RELAY
PIN
1
Fire Relay Common
2
Fire Relay Normally Closed
3
Fire Relay Common
4
Fire Relay Normally Open
J5:
FAULT RELAY (Energized)
PIN
1
Fault Relay Normally Open
2
Fault Relay Common
3
Fault Relay Normally Closed
4
Fault Relay Common
J6:
FIRE VERIFY RELAY
PIN
1
Verify Relay Common
2
Verify Relay Normally Open
3
Verify Relay Common
4
Verify Relay Normally Closed